[Retracted] Research on Protection Performance of Surge Protective Devices against Electromagnetic Pulse
Table 4
Test results of MOV’s ability to suppress electromagnetic pulse.
| | Pulse type | Narrow pulse | Wide pulse | | Number of times | Injection voltage peak | Device response residual voltage peak
| Injection voltage peak | Device response residual voltage peak
|
| | 1 | 258 | 117 | 400 | 390 | | 2 | 430 | 137 | 612 | 610 | | 3 | 622 | 202 | 740 | 730 | | 4 | 932 | 316 | 950 | 840 (790) | | 5 | 1252 | 408 | 1170 | 864 (808) | | 6 | 1650 | 520 | 1470 | 876 (780) | | 7 | 1850 | 592 | 1770 | 888 (796) | | 8 | 2130 | 648 | 1930 | 912 (800) | | 9 | 2430 | 740 | 2470 | 984 (948) | | 10 | 2790 | 820 | 2770 | 1008 (980) | | 11 | 3030 | 880 | 3170 | 1168 (992) |
|
|
Note: The voltage in brackets is the clamping voltage, and the nominal value of the device is 621 V.
|