Research Article

[Retracted] Research on Protection Performance of Surge Protective Devices against Electromagnetic Pulse

Table 5

Test results of TVS’s ability to suppress electromagnetic pulse (TVS type is 1.5KE36CA).

Pulse typeNarrow pulse(10/100 ns)Wide pulse(10/700 μs)
Number of timesInjection voltage peak
Device response residual voltage peak
Injection voltage peak
Device response residual voltage peak

163262.829638.4(35.2)
294480.497639.6(38.1)
31590109172040.8(38.5)
41820120268042.1(40.8)
52260144324049.2(41.1)
62700144360049.6(41.9)

Note: The voltage in brackets is the clamping voltage, and the nominal value of the device is 36 V.