Research Article
[Retracted] Research on Protection Performance of Surge Protective Devices against Electromagnetic Pulse
Table 5
Test results of TVS’s ability to suppress electromagnetic pulse (TVS type is 1.5KE36CA).
| | Pulse type | Narrow pulse(10/100 ns) | Wide pulse(10/700 μs) | | Number of times | Injection voltage peak
| Device response residual voltage peak
| Injection voltage peak
| Device response residual voltage peak
|
| | 1 | 632 | 62.8 | 296 | 38.4(35.2) | | 2 | 944 | 80.4 | 976 | 39.6(38.1) | | 3 | 1590 | 109 | 1720 | 40.8(38.5) | | 4 | 1820 | 120 | 2680 | 42.1(40.8) | | 5 | 2260 | 144 | 3240 | 49.2(41.1) | | 6 | 2700 | 144 | 3600 | 49.6(41.9) |
|
|
Note: The voltage in brackets is the clamping voltage, and the nominal value of the device is 36 V.
|