Research Article
[Retracted] Research on Protection Performance of Surge Protective Devices against Electromagnetic Pulse
Table 7
Test results of Zener diode’s ability to suppress narrow pulse (10/100 ns).
| | Pulse application mode | Forward application | Reverse application | | Number of times | Injection voltage peak
| Device response residual voltage peak
| Injection voltage peak
| Device response residual voltage peak
|
| | 1 | 13.5 | 1.6 (0.74) | 53.0 | 31.0 (23.0) | | 2 | 56 | 5.08 (0.74) | 78.4 | 32.8 (28.0) | | 3 | 96 | 8.76 (0.72) | 101.0 | 43.2 (28.0) | | 4 | 120 | 9.12 (0.72) | 132.0 | 54.5 (29.2) | | 5 | 142 | 10.2 (0.72) | 162.0 | 52.4 (29.2) | | 6 | 186 | 21 (0.80) | 224.0 | 70.0 (30.0) | | 7 | 221 | 22.8 (0.80) | 249.0 | 74.8 (30.0) |
|
|
Note: The voltage in brackets is the clamping voltage value.
|