Relationship between Damage Rate of High-Voltage Electrical Equipment and Instrumental Seismic Intensity
Table 2
Gaussian distribution accumulation function curve parameter values of high-voltage electrical equipment damage rate.
Equipment type
Transformer
8.21
1.14
Circuit breaker
9.26
0.88
Isolating switch
10.03
1.48
Lightning arrester
9.68
1.26
Current mutual inductor
9.92
1.36
Voltage mutual inductor
9.67