Research Article
Analysis and Research on Energy-Saving Reconstruction of Building Heating System
Table 4
The number of radiators in each building and its heating capacity.
| | 
 |  | Building | Number of radiators per square meter, n (slice/m2) | Heat release of each radiator when the supply and return water temperatures are 65/58°C and the indoor temperature is 16°C, q2 (W/piece) | The heat supply per square meter when the supply and return water temperatures are 65/58°C and the indoor temperature is 16°C (Qs2 = q2)n, (W/m2) |  | 
 |  | Office building | 0.69 | 63.48 | 66.7 |  | Advanced water treatment workshop | 0.63 | 57.96 | 60.9 |  | Chemical feed room | 0.71 | 65.32 | 68.6 |  | Other workshops | 0.63 | 57.96 | 60.9 |  | 
 | 
 |