Research Article
Analysis and Research on Energy-Saving Reconstruction of Building Heating System
Table 5
Parameters of main equipment.
| | 
 |  | Equipment number | Equipment name | Equipment parameters |  | 
 |  | 1 | Water-source heat pumps | The heating capacity under design condition is 702 kW |  | 2 | Plate heat exchanger | The heat transfer capacity under design condition is 550 kW |  | 3 | Circulating water pump | The flow rate is 120 m3/h, the lift is 8 m H2O |  | 4 | Circulating water pump | The flow rate is 73 m3/h, the lift is 32 m H2O |  | 5 | Water softener | The water treatment capacity is 1.0 m3/h |  | 6 | Soft water tank | The volume is 1.0 m3 |  | 7 | Make-up water pump | The flow rate is 1.0 m3/h, the lift is 22 m H2O |  | 8 | Pressure tank | The regulating volume is 0.2 m3 |  | 
 | 
 |