Abstract

Near-field pulse-type ground motions (NPGMs) are characterized by a high-energy pulse with large peak ground velocities and accelerations and need further studies to confirm whether structures with viscous dampers (VDs) are still applicable and effective for this type of ground motions. In this article, the vibration reduction performance of structures with VDs under near-field earthquakes is investigated systematically. Displacement and acceleration spectra are developed for a single-degree-of-freedom (SDOF) structure with and without VDs, while these influence factors, such as the nonlinear characteristic of structure, damper supports’ flexibility, and damper parameters, are considered. Additionally, the frequency domain characteristics of NPGM and the energy distribution of a multidegree-of-freedom (MDOF) structure with VDs are discussed to further reveal the action mechanism of NPGM on the structure. It is shown that the structure with VDs shows remarkable seismic reduction effect under the action of near-fault pulse-type earthquake, and the maximum interstorey drift decreased from 0.086 to 0.037 when the structure is equipped with VDs. However, the structure may still be difficult to completely dissipate the high-energy generated by the earthquake pulse with a high pulse period in a short time, which can cause the structure to be damaged or even collapsed in a moment.

1. Introduction

In recent years, considerable passive energy dissipation devices, such as viscoelastic dampers, metallic yield dampers, friction dampers, and fluid viscous dampers [1], have been widely applied in structures to enhance their energy dissipation capability, which can reduce the seismic response of the structure under ordinary ground motions obviously [2, 3]. Among these devices, fluid viscous dampers are more prevalent due to its wide frequency band of vibration attenuation [4], low cost, and easy maintenance. However, in recent major earthquakes (Northridge 1994, Chi-Chi 1999) [57], a type of near-field pulse-type ground motion (NPGM) has been found. It is characterized by a high-energy pulse with large peak ground velocities and accelerations, which can cause more serious damage to structures than ordinary ground motions, and many research literature studies [812] have confirmed this adverse effect. Therefore, whether structures with viscous dampers (VDs) are still applicable and effective for this special type of ground motions needs further study.

It has to be recognized that, for strong earthquakes, most structures employing VDs will experience some level of inelastic response [13], which may cause significant increases in the base shear; therefore, the nonlinear influence of structures on the seismic responses should be considered. Kumar [14] investigated the seismic performance of multistorey structures strengthened with nonlinear viscous dampers. Güler and Alhan [15] compared the seismic performance of the base-isolated liquid storage tanks with/without supplemental damping. Yaghmaei-Sabegh et al. [16] proposed a modified direct method to estimate the seismic response of structures equipped VDs under near-field pulse-like ground motions. Xu et al. [17] investigated the performance of an SDOF structure with VDs when it is subjected to NPGM, and the conclusion indicated that the structural displacement can be reduced significantly when the ratio of structure to excitation periods is in a certain range. Yi et al. [18] proposed to use a negative stiffness device combined with FVD for the bridge and investigated the seismic response of the bridge under near-fault earthquakes. The results indicated that the acceleration and the deck displacement of the bridge can be reduced.

This article extends Ref. [17], which focuses on the vibration reduction performance of structures with VDs under near-field earthquakes, and these influence factors such as the nonlinear characteristic of structure, damper supports’ flexibility, and damper parameters are considered. The state-space representation is used to describe structures with VDs, and the seismic response of the structure under four groups of NPGM with different pulse periods is calculated and compared. Furthermore, the dissipated energy distribution of the structure and the frequency domain characteristics of NPGM are employed to further reveal the action mechanism of NPGM on the structure.

2. Modelling of Structures with VDs in State-Space Representation

2.1. SDOF

An SDOF structure with VDs is presented in Figure 1(a), where the supplementary VD is connected to the structure through a linear elastic supporting brace, and the Maxwell model is used to describe its mechanical behaviour. It is comprised of a purely viscous damper with damping coefficient and a purely elastic spring with stiffness . Figures 1(b) and 1(c) show the prototype of viscous damper.

The dynamic equation of an SDOF structure with VDs subjected to ground motion can be described by means of the following equation:

where , , and are the structural mass, inherent damping coefficient, and lateral stiffness, respectively; and , , and represent the responses of displacement, velocity, and acceleration, respectively. Note that consists of two parts: the displacement of VD and the elastic deformation of the supporting brace. In the following, the exponent of VD controls the damper nonlinearity and its typical values is in the range of 0.2–1 [3, 1921] for seismic applications:

In this article, the influence of in the range of 0.3–1 on the vibration reduction performance of the structure has been discussed.

Assuming that the brace stiffness is proportional to the lateral stiffness of the structure, and the damper coefficient is proportional to the damping of the structure [22], two dimensionless parameters can be respectively defined as

Hence, and can be replaced by the above equation [23], and the resulting equation is divided by m to obtain the following:where and are the circular frequency and the damping ratio of the structure, respectively. For the convenience of calculating the seismic response of the structure, the state-space representation has been used to transform second-order differential equations (4) and (5) into first-order differential equations and the structural displacement; velocity and the VD’s displacement are selected as state variables, which is shown in the following equation:where is a column vector of the equations; , , and are the supplementary matrix with constant elements, respectively, which can be written as

Note that all the variables change with , which vary with time at a high rate, and equation (5) contains a series of stiff equations; therefore, Gear’s backward numerical differential algorithm is chosen to solve the equations.

However, when the structure enters into an elastoplastic state under strong earthquake, the influence of stiffness degradation on the seismic response of the structure should be considered, and therefore, the frequently used bilinear elastoplastic model (Figure 2) has been employed to describe the nonlinear characteristic of the structure. Now equation (1) of an SDOF structure with VDs can be rewritten as

At the same time, the strength reduction factor and ductility factor are defined aswhere is the ratio of the maximum elastic force to the yield force of the structure, is the structural maximum elastic acceleration, and the yield force can be expressed as ; is the ratio of the maximum inelastic displacement to the yield displacement of the structure, and is the elastoplastic restoring force. In order to obtain the inelastic seismic response of the structure under the condition of equal strength or equal ductility, the in equation (8) can be replaced by equation (9); thus, a new equation is defined as

Based on equations (10) and (2), the inelastic seismic response of the structure can be obtained with the state-space method when is determined.

2.2. MDOF

For a n-storey structure equipped with VDs at each storey, the bilinear elastoplastic model has been used to describe the characteristic of cyclic behaviour of the structure in each storey at the same time, and its dynamic equation can be expressed aswhere and are the structural mass and damping matrices; is the vector of structural displacements; is the vector of the elastoplastic restoring forces; and is a unity vector; is the vector of damper forces. Now the state-space representation has been employed to convert equation (11) into an array of first-order ordinary differential equations, which is shown aswhere the state variable is a vector that contains the structural displacements , velocities , and plastic displacement components ; the matrices, and are auxiliary conversion matrices, which can be determined as follows:where and are the structural elastic stiffness and plastic stiffness matrices, respectively; and are the zero matrices and unity matrices, respectively; is a vector, which represents the plastic hysteretic characteristics of the structure; is the damper force for the i-th storey, and it can be written as

Combining equations (12) and (14) and using Gear’s backward numerical differential algorithm to solve the equations, the inelastic seismic response of the MDOF structure with VDs under strong earthquakes can be obtained.

3. Selection of NPGM

Based on the method of regionalization of near-field seismic region proposed by Ming [24], a number of near-field ground motions of strike-slip faults mechanism with moment magnitude greater than 5.5 were selected from the Pacific Earthquake Engineering Research (PEER) Center. Then, a pulse indicator was proposed by Baker [25], which has been employed to identify whether a given record is pulse-like. shown in equation (15) takes values between 0 and 1, with a higher value indicating that the record is pulse-like, and the record can be classified as pulse when is greater than 0.85. The PGV ratio is the value of the peak ground velocity (PGV) of the residual record divided by the original record’s PGV, and the energy ratio is the value of the energy of the residual record divided by the original record’s energy [25]:

Finally, 24 pulse-type ground motions have been picked out based on the above method and divided into four groups (G1∼G4) in accordance with its pulse period . The four groups can be defined as follows: when , the ground motions are classified as the G1 group; when , the ground motions are classified as the G2 group; when , the ground motions are classified as the G3 group; when , the ground motions are classified as the G4 group, which are shown in Table 1.

4. Analysis of the Influence Factors and Vibration Reduction Performance

4.1. Analysis of Influence Factors
4.1.1. Influence of the Parameters of VD

It is clear to see that the seismic response of the structure varies directly with the values of , and on the basis of equations (4), (5), and (8). Thus, before further studying on the vibration reduction performance of the whole structure, we should understand the influence of these parameters on the seismic response of the structure in detail. In order to clarify the characteristics of its influence, now record no. n1114 obtained from the 1995 Kobe Japan earthquake is selected as excitation, and the seismic response of an elastic SDOF structure with VDs (ETD) and its corresponding uncontrolled structure (UST) are calculated.

Figures 3(a) and 3(b) show the curves of the displacement ratios of ETD to UST varying with the parameters and for different structural periods ( and , which represent the short period structure and the long period structure, respectively), and Figures 3(c) and 3(d) show the varied curves of the acceleration ratios of the corresponding structures mentioned above. Here, and are the maximum elastic displacement responses of ETD and UST, respectively. and are the maximum elastic acceleration responses of ETD and UST, respectively. It is observed from Figures 3(a) and 3(b) that decreases with an increase in when equals 2, which indicates that the vibration reduction effect of ETD can be improved by increasing the value of within a certain range and the effect can remain stable when exceeds the range. Furthermore, it can be found that the vibration reduction effect will be more significant when the exponent of the VD is smaller and the structural period is shorter. However, with the period increasing from 0.6 s to 2.0 s (the corresponding circular frequency decreasing from 10.47 to 3.14), the difference of influence of with different values on the vibration reduction effect of ETD gradually decreased. When equals 2.0 s, the effect is basically the same no matter what value takes in the range of 0.3–1.0. It can be clearly found that the acceleration response of the structure has also the similar change rule, as shown in Figures 3(c) and 3(d).

Moreover, Figures 3(e) and 3(f) show the corresponding displacement ratios of VD to ETD. It can also be observed that the ratio of varies with the change of and . For a damper with a smaller exponent , a larger value of is needed when the displacement of the damper becomes closer to the displacement of the structure, namely, .0. But with the increase in the period , the influence of on the minimum value of , which keeps the ratio of constant, is gradually weakened.

Based on the above analysis, it is recommended that the minimum range of , which can help to take full use of the energy dissipation capacity of the damper, is between 3 and 6 for the different values of and periods of the structure. Namely, the minimum value of should not be less than 6 when equals 0.3, and should not be less than 3 when equals 1.0, which can help to make full use of the energy dissipation capacity of dampers. When is between 0.3 and 1.0, can be determined by linear interpolation. Once the value of is determined, the minimum value of can also be determined according to the structural period and the coefficient of VD.

In addition, in order to further illustrate the influence of on the vibration reduction effect of ETD, Figures 4(a) and 4(b) show the curves of the displacement ratios of ETD to UST varying with the parameters and when the natural vibration period of the structure equals 2.0 s. Figures 4(c) and 4(d) show the curves of the acceleration ratios of the corresponding structures mentioned above. Figures 4(e) and 4(f) show the curves that the corresponding displacement ratios of VD to ETD. It can be observed from Figures 4(a)4(d) that and decrease significantly with the increase of , which indicates that the vibration reduction effect of the structural displacement and acceleration is remarkable, and the ratios of have the similar changing trends and less affected by the different values of and , as shown in Figures 4(e) and 4(f). Besides, it has to be noted that whether the energy dissipation capacity of the damper can be sufficiently utilized mainly depends on the parameter , which is relative stable and dimensionless. It is observed that the linear VD ( = 1.0) can be sufficiently utilized and is almost not affected by the damper coefficient and other influence factors when equals 3; while for the nonlinear VD (), the minimum value of is affected by the parameters and . Namely, a smaller exponent and a higher coefficient usually require a larger value of , which can contribute to making full use of the energy dissipation capacity of the damper. Nevertheless, when equals 6, the nonlinear VD () can basically be fully utilized, which indicate that the range of between 3 and 6 is suitable for the change of exponent in the range of 0.3–1.0.

4.1.2. Influence of Other Factors

Additionally, it is well known that the ground motions are characterized by great uncertainty; therefore, different ground motions have been selected as excitations and the seismic responses of the structure with VDs are calculated and compared according to the above methods. It can be found that the influence of these parameters on the structure under different ground motions is similar to the above analyzed conclusions, which can be used to demonstrate that the influence rules mentioned above are general. However, it should be realized that the demands for dampers of the structure under different ground motions are different, and sometimes, the amount of the dampers are excessive when the structure is subjected to some near-fault ground motions, which may lead to amplify the acceleration response of the structure although the displacement response of the structure can be reduced, as shown in Figures 5(a) and 5(b). The results confirm that an optional damping is needed to balance the reduction of structural displacement and the increase of the total acceleration [14].

At the same time, the influence of stiffness degradation on the seismic response of the structure is considered, and the displacement response spectra SD of an SDOF structure with and without VDs are compared, as shown in Figure 5(c). It can be observed that the inelastic displacement of the uncontrolled structure shows a certain degree of discreteness relative to the elastic displacement when the structure enters into an elastoplastic state; however, when it is equipped with VDs, the displacement of the structure shows no obvious change in the elastic state and the elastoplastic state. The result indicates that the damper can effectively restrain the adverse effects of discrete deformation caused by stiffness degradation when the structure enters into an elastoplastic state.

4.2. Analysis of Pulse-Type Spectra

Now these parameters of , 4, and are determined on the basis of the above conclusions, which have been used to calculate spectra for an elastic SDOF structure with VDs (ETD) and an elastoplastic SDOF structure (R = 4) with VDs (PTD) when the structure is subjected to NGPM, which is shown in Table 1; at the same time, the spectra for an uncontrolled SDOF structure (UST) are also given as a contrast, and the spectra in the range of 0.1–10 s are shown in Figure 6. Additionally, two dimensionless displacement coefficients ( and ) and two dimensionless acceleration coefficients ( and ) are defined aswhere , , and are the spectral displacement of UST, ETD, and PTD, respectively; , , and are the corresponding spectral acceleration.

It is observed from Figures 6(a) and 6(d) that SD increases with an increase in , and the peak displacement response occurs when . Meanwhile, the attenuation rate of SA slows down with an increase in . However, when the structure is equipped with VDs, a quite different vibration reduction effect of ETD is presented in different period ranges, as shown in Figures 6(b) and 6(e). For the ground motions of the G1 group, the vibration reduction effect of SD is remarkable when is between 0.1 s and 2.0 s, but once it goes out of this range, the displacement of ETD will not be significantly reduced or even amplified. Moreover, the acceleration response of ETD is also amplified when is more than 1.0 s, which indicates that only in a certain range of period can the energy dissipation capacity of the damper be utilized efficiently when the structure is subjected to NPGM with pulse periods less than 1.0 s. For the ground motions of G2∼G4 groups, SD and SA increase with an increase in , which can lead to an increase in demands for dampers at the same time and that enables the damper to be utilized efficiently in a wider range of period. The displacement response of PTD shows no apparent change relative to that of ETD when the structure enters into an elastoplastic state, but its corresponding structural acceleration response is slightly reduced, as shown in Figures 6(c) and 6(f), which indicates that the adverse effect of stiffness degradation on the seismic response of PTD can be significantly reduced when the structure is equipped with VDs. Moreover, the similar results can also be obtained with different and values, and R changes in the range of 2–8.

Figure 7 shows the plots of the normalized spectra of SD and SA as the function of period ratio for ETD and PTD (R = 4) subjected to NPGM. Figures 7(a) and 7(b) show and normalized displacement spectra for ETD and PTD, respectively. It is observed from Figures 7(a) and 7(b) that the reduction in displacement is not obvious when , even amplified for PTD, and relative higher reduction can be obtained for . However, the displacement response of ETD and PTD shows great discreteness when .

Figures 7(c) and 7(d) show and normalized acceleration spectra for ETD and PTD (R = 4), respectively. It is observed from Figures 7(c) and 7(d) that the characteristic of reduction in acceleration is similar; that is, reduction in acceleration is not obvious when , and most of acceleration responses are amplified. However, larger reduction can be obtained for , and it is amplified for both elastic and elastoplastic structures when .

4.3. Energy Response of Pulse-Type Excitation

To investigate the energy distribution characteristic of structure with VDs when it subjected to NPGM, the energy balance approach has been employed to analyze the cumulative energy response for the structure. The cumulative energy response for the structure in equation (8) can be obtained by integrating (8) with a displacement increment aswhere each integral expression represents the cumulative energy from 0 to t time. The first and second terms on the left side of equation (17) represent kinetic energy and inherent damping energy , respectively, and the third term is the strain energy, which includes elastic strain energy and plastic strain energy . The fourth term on the left side of equation (17) is the energy dissipated by VD, and it can be calculated as

The total seismic input energy on the right side of equation (17) can be written as

Figure 8 shows time-history plots of the accumulative energy response that include seismic input, kinetic, inherent damping, strain, and dissipated energies for an uncontrolled SDOF structure and the structure with VDs subjected to pulse excitation. It is observed from Figure 8(a) that, for the uncontrolled structure, the seismic input energy of ground motions is dissipated mainly by plastic strain energy and inherent damping energy once the structure enters into an elastoplastic state, which indicates that it may suffer severe damage. While for the structure with VDs, the total input energy is dissipated mainly by the hysteresis energy of VD as shown in Figure 8(b), and the proportion of plastic strain energy to total input energy is significantly reduced.

Figure 9 shows the plots of the max seismic input energy as a function of for structures subjected to some pulse excitations. In Figure 9, represents the ratio of the max seismic input energy of structure with VDs to the uncontrolled structure. It is observed from Figure 9(a) that peak input energy of the uncontrolled structure occurs when .

When structure is equipped with VDs, a smaller value of in the range of can be found, which implies that the most significant reduction in seismic input energy occurs when, while the input energy of structure with VD is amplified when , which is shown in Figure 9(b). This can be used to explain why the seismic response of the structure with VDs in Figures 7(b) and 7(d) is not reduced or even amplified when .

5. Numerical Example

In order to further reveal the action mechanism of near-fault ground motions on structure with VDs, a characteristic twelve-storey steel frame is presented, as shown in Figure 10, whose seismic performance has met the requirement of the Chinese design code (GB50011). The bottom storey height is equal to 4.0 m and the others are 3.6 m, and all the materials are standard steel grade Q355. Columns consist of standard BOX sections, beams consist of standard middle flange H-type sections (HM) and narrow flange H-type sections (HN), and the more detailed information is presented in Table 2. The frame is subjected to a uniform floor dead load 4.7 kN/m2 on each storey. The floor live load is 4.0 kN/m2 for the first to sixth storeys and 2.0 kN/m2 for the seventh to twelfth storeys. Furthermore, the bilinear elastoplastic model has been used to describe the characteristic of nonlinear behaviour of the structure, and the ratio of postyielding stiffness to elastic stiffness of the structure is 0.02.

The condensed elastic stiffness matrix and plastic stiffness matrix of the structure can be expressed as

5.1. Modal Analysis of MDOF Structure

To investigate the dynamic characteristic of this frame, the first three mode shapes of the structure in X direction are presented in Figure 11 when the structure enters into different states: the elastic structure in Figure 11(a), elastoplastic structure with yield of the first storey in Figure 11(b), elastoplastic structure with yield of the first to third storeys in Figure 11(c), and elastoplastic structure with yield of the first to sixth storeys in Figure 11(d). It is observed from Figure 11(a) that the modal participating mass ratio of the first three mode shapes is more than 90%, which indicates that the response contributions of the three modes are enough to obtain the exact value of the structural response. When the first storey of the frame yields, the first mode shape is characterized by translational motion, as shown in Figure 11(b). Furthermore, the amplitude of the mode shapes is mainly grouped in the yielded storeys when the storeys yield gradually from bottom to top of the structure, which is shown in Figures 11(c) and 11(d). In summary, it can be concluded that when the structure enters into an elastoplastic state, its dynamic characteristic is quite different from that of its corresponding elastic structure, and its displacements of the storeys that are in an elastic state are significantly reduced by shifting the response to the other storeys that are in an elastoplastic state.

5.2. Seismic Response and Its Characteristic

In this section, to show the effect of NPGM on the frame, the nonlinear time history analysis is employed to evaluate the performance of the structure under pulse-type excitations in X direction. The structure is excited by the ground motions shown in Table 1, and their peak ground accelerations (PGA) are scaled down to 0.4 g to commensurate with the PGA under major earthquakes of intensity 8, and the results are shown in Figure 12.

Figure 12 shows the plots of the interstorey drifts and accelerations of the structure. It is observed from Figure 12(a) that the range of interstorey drifts under NPGM in X direction is large and most of them exceed the Chinese code limitation, but this trend of change is basically similar. Furthermore, it can be found from the average interstorey drifts of the corresponding G1∼G4 groups that the structural interstorey drifts under G1 group are small, while it gradually increases and exceeds the code limitation 1/50 under G2∼G4 groups with the increase in pulse periods. It indicates that this kind of ground motions with a large pulse period can cause serious damage to the structure, and the damage is mainly concentrated in the middle and lower storeys of the structure. At the same time, it can be found that the structural average accelerations under the corresponding G1∼G4 groups are similar, as shown in Figure 12(b), which implies that the PGA is not a good intensity measure to quantify the damage potential of pulse-type ground motions although it can affect the structural seismic response.

In order to investigate the vibration reduction performance of the structure with VDs under pulse-type ground motions, the number of dampers and configurations are presented in Table 3 based on the above analysis, and the results of the nonlinear time history analysis are shown in Figure 13.

Figures 13(a) and 13(b) present the comparisons of maximum seismic responses of the steel frame with and without VDs. It can be found that the maximum interstorey drifts and maximum absolute accelerations are significantly reduced when the structure is equipped with VDs, and the responses are not amplified under any pulse-type excitation, which is completely different from the elastoplastic response characteristics of the SDOF structure. However, the maximum interstorey drifts of some stories still exceed the code limitation under some pulse-type excitations. This result implies that the seismic performance of the structure can be significantly improved by applying VDs, but its demand for dampers is enormous, and the structure still has the risk of local failure, even overall collapse under some pulse-type excitations. Now, record no. n180 obtained from the 1979 Imperial Valley earthquake is taken as an example to carry out a detailed analysis.

The maximum interstorey drift of the uncontrolled structure under pulse-type excitation of record n180 is 0.0859, and it occurs at the fourth storey, while it decreased from 0.086 to 0.037 when the structure is equipped with VDs. Figures 14(a) and 14(b) show the plots of the time history of displacement and acceleration at the fourth storey. It is observed that the responses of displacement and acceleration are significantly reduced when the structure is equipped with VDs, but it still appears permanent deformation. The main reason for the results is that the main energy of the record is in a relatively narrow and low-frequency band, and most stories of the structure gradually yield under a certain intensity of the record, which leads to an obvious reduction in the structural main natural frequencies. When the structural main natural frequencies approached the frequency band which the main energy of the record concentrated in, it may cause resonance and serious damage to the structure. Such as in Figure 15(a), when the structural second to fifth storeys yielded, the second natural frequency of the structure is just in the frequency band where the peak energy is recorded. However, the main natural frequencies are changed when the MDOF structure is equipped with VDs, as shown in Figure 15(b), which can help to alleviate these adverse effects.

Figure 16 shows the time history plot of the energy for the steel frame with VDs, at the same time, combined with the deformation characteristics of the structure in Figure 14(a); it can be found that the seismic input energy of n180 increases sharply in the range of 6.0–8.0 s, and it is difficult for the damper to dissipate the high instantaneous input energy generated by the record in a short time. The energy dissipation rate of the damper obviously lagged behind the increase rate of the seismic input energy of the record, which led to an increase in the plastic strain energy of the structure. This characteristic is unlike SDOF structure with VDs in Figure 8(b), and it demonstrates that the characteristics of action mechanism and seismic response of the MDOF structure are completely different from that of the SDOF structure with VDs.

6. Conclusions

In this article, the vibration reduction performance of structures with viscous dampers under near-field pulse-type ground motions has been examined via response spectrum and energy balance analysis, and the influence of various factors, such as parameters of VD, nonlinear parameter of structure, and the characteristic of ground motions, are considered. The characteristics of seismic response and energy dissipation of SDOF structure and MDOF structure are compared, which have been employed to further reveal the action mechanism of pulse-type ground motions on structures with VDs. The main conclusions of this research are the following:(1)The parameter has a significant impact on the vibration reduction performance of the structure. It is recommended that the minimum value of should not be less than 6 when equals 0.3, and should not be less than 3 when equals 1.0.(2)The MDOF structure with VDs will enter into an elastoplastic state under most of pulse-type ground motions, and its main natural frequencies are constantly changing, which make its dynamic performances more complicated than that of the SDOF structure. The characteristics of vibration reduction of the SDOF structure with VDs under pulse-type ground motions may not be applicable to the MDOF structure due to its more complicated dynamic behaviours.(3)The viscous damper can significantly reduce the seismic response of the structure under pulse-type ground motions, but the required number of VDs is enormous, and the structure with VDs may still be difficult to completely dissipate the instantaneous input energy in a short time when it is subjected to a pulse-type ground motion with a high pulse period. Usually, it can cause the structure to be damaged or even collapsed in a moment when the energy dissipation rate of the damper obviously lagged behind the increase rate of the seismic input energy of the record.

Data Availability

The data used to support the findings of this study are included within the article.

Conflicts of Interest

The author declares that there are no conflicts of interest or personal relationships that could have appeared to influence the work reported in this article.