Abstract

This paper discusses the deformation mechanism of a utility tunnel crossing active ground fissures in Xi’an as observed in a physical model test. The purpose of this work is to confirm the precise effects of ground fissures on utility tunnels. The physical simulation experiment is carried out to measure the earth pressure and the strain relationship of the structure and the structural displacement. The structure appears to have been destroyed by torsion. The structural deformation located in the tunnel’s footwall was more serious than that in the hanging wall. However, at the top of the utility tunnel structure, the earth pressure in the footwall was less than that in the hanging wall. The increased range of the hanging wall at 0.3–1.5 m (the prototype within the range of 22.5 m) and decreased range of the footwall at 0.3–0.8 m (the prototype within the range of 12 m) were basically consistent with changes in the contact pressure at the structure’s bottom. This was roughly consistent with the main deformation zone of ground fissures mentioned in the specification, with the hanging wall at 0–20 m and footwall at 0–12 mm. Displacement meter data shows that the structure tends to deform to the lower right as the utility tunnel is “twisted” clockwise. These observations mark a notable departure from the previously published failure mode of metro tunnels under active ground fissures.

1. Introduction

The ground fissure is a serious geological hazard which is common in many countries. Ground fissures were first discovered at the Goose Greek Oil Field near Houston, Texas, USA, in the 1920s. By the end of the 1950s, ground fissures were identified in China [19]. Ground fissures may become geological disasters that threaten the roads, buildings, and pipelines surrounding them. Throughout Shandong, Anhui, Jiangsu, Shanxi, Shaanxi, and Henan provinces, active ground fissures are a crucial consideration in effective city planning [1021].

Ground fissures form based on the development of the nearby fault structure and the excessive exploitation of groundwater [7, 13, 18]. The excessive extraction of groundwater since the 1950s has produced fourteen ground fissures in the city of Xi’an [3, 16]. The appearance of ground fissures, resulting in the destruction of many surface buildings and underground construction facilities, has so far caused billions of direct economic losses in Xi’an. Existing ground fissures continue to develop as new ground fissures appear, which severely restrict the effective use of urban construction land in Xi’an and the construction of new urban projects [3, 16, 22, 23].

Ground fissures in Xi’an typically undergo normal fault-type peristaltic movement wherein the hanging wall slides relative to the footwall; the vertical displacement typically shows unidirectional accumulation. Ground fissures activity profile characteristics of the city of Xi’an are shown in Figure 1. The ground fissure tends to the south at a steep dip angle, generally above 70°. The ground fissure zone features three-dimensional spatial movement comprised of vertical displacement, horizontal displacement caused by north-south tension, and horizontal dislocation at a ratio of 1 : 0.31 : 0.03. When a structure obliquely crosses the ground fissure, the activity of the ground fissure generates three-dimensional spatial displacement motion in the structure, that is, vertical, transverse, and axial displacement occurring simultaneously. The tensile displacement of ground fissures in Xi’an is generally under 10 m and the fissures are nearly closed, while the buried depth of utility tunnels in the area is generally less than 10 m. Utility tunnels crossing the ground fissure zone in Xi’an are designed without considering the effects of tensile and torsional ground fissure components on the structure—only the effect of the vertical displacement is taken into account.

To quantitatively evaluate the impact of the formation and development of ground fissures on the stress field distribution of surrounding soil and building deformation under stress, researchers in related fields have performed many studies in the past few years and large-scale physical model tests have been effective research methods. Peng et al. [24], Huang et al. [25], Fan et al. [26], and Hu et al. [27] have conducted extensive physical model tests of metro tunnels passing through ground fissure zones. Existing research results have systematically revealed the causes and characteristics of ground fissures and their effects on underground structures, especially subway tunnels, but research on the effects of deformation and failure characteristics of utility tunnels across ground fissures has been still relatively rare.

Although utility tunnels and subway tunnels are both underground structures, the buried depths and structural cross sections are different. Most subway tunnels are one cabin, and a utility tunnel is basically more than two cabins, and the resulting structural section is thus more complicated. Previous studies have shown that the smaller the horizontal angle between the long-line underground structure and the ground fissures, the more the influence of ground fissures motion. As ground fissures in the city of Xi’an are basically distributed in parallel along the northeast-southwest direction, they form a 45° angle with existing planned utility tunnels (Figure 2). Therefore, this study addresses the Xi’an utility tunnel construction PPP project I bid-section of the Yanta District Kechuang Road utility tunnel project as the research background, according to its geological survey report, combined with existing ground fissure survey results. Research data speculates that the Xi’an ground fissure f6 develops on the east side of the construction site. This study intended to carry out a physical model test on the deformation and failure mode of the utility tunnel with a 45° oblique penetration of the ground fissure. The model test was designed with a geometrical scale of 1 : 15. Based on the analysis of structural strain, earth pressure, and structural displacement under the active ground fissure zone, the deformation modes of the utility tunnel structure were summarized. It was anticipated here to supply a certain reference for the design and construction of a utility tunnel projecting through a ground fissure zone.

2. Model Test

2.1. Physical Model Test Equipment

Figure 3 is the physical model test equipment applied in this study. The testing equipment has dimensions of 5.0 m length, 2.5 m width, and 2.5 m height. The hanging wall descends relative to the footwall; the footwall is stable (Figure 1). To simulate the temporal effects of ground fissures, the equipment was equipped with self-locking jacks to slowly descend. The settlement of the hanging wall in this model test was 80 mm and was applied in eight stages. The inclination of the ground fissure in the experiment was 80 degrees (Figure 3). Strain gauges were used to test the mechanical deformation and earth pressure cells were used to test the earth pressure under the displacement of the ground fissure. The test principle is shown in Figure 3.

2.2. Model Test Similar Ratio

According to the similarity principle [28], the geometry similarity ratio , and the concrete elastic modulus similar constant ; a similar relationship between other physical quantities can be established as shown in Table 1. The model utility tunnel cross section is shown in Figure 4.

2.3. Model Similar Material

In this test, the surrounding soil used loess-like soil; soil material parameter values include the following:γ = 18.6 kN/m3γ—soil bulk densityE = 9 MPa E—modulus of elasticityν = 0.35 ν—Poisson’ ratioC = 0.025 C—cohesionφ = 24 φ—internal friction angle

The model concrete was cast from fine aggregate concrete with a certain amount of steel mesh inside. The model utility tunnel was fabricated from fine aggregate concrete. The parameters determined according to a series of multiple ratio tests prior to testing are shown in Table 2. The mix ratio of the model’s fine aggregate concrete is shown in Table 3.

The rebar (short for reinforcing bar) rate of the structure is determined by the principle of equal strength, as shown in the following formula:where and are prototype reinforcement and concrete area. is tensile strength of prototype reinforcement. is compressive strength of prototype concrete. and are model reinforcement and concrete area. is tensile strength of model reinforcement. is compressive strength of model concrete.

The dip angle of the ground fissure is 80° according to the measurements taken during the ground fissure simulation with fine sand.

2.4. Test Contents and Data Collection

The rows of 45° strain flowers were arranged at the top, bottom, and sides of the model with nine flowers in each row to measure strain in different directions of the utility tunnel lining. A layout of the measurement points is shown in Figure 5.

At the intersection of the structural axis and the ground fissure, which is 0.25 m on each side, strain gauges were arranged on stirrups on three sections, which were used to test the circular strain of the structural steel. The section located the axial midpoint of the structure (Figure 6).

Ten sections were arranged along the axial direction of the structural steel with eight measuring points on each section to measure the longitudinal strain of reinforcement at the top and bottom of the structure (Figure 7).

A total of eight measuring lines were arranged along the axial direction of the structure—three at the top and five at the bottom—to test the changes in longitudinal earth pressure during the experiment. Five sections were arranged perpendicular to the axis of the structure with two measuring lines each. The top and bottom of the structure were equipped with five measuring lines to determine changes in transverse earth pressure during the experiment. One measuring line was arranged on the north and south sides of the structure. Each measuring line was equipped with seven earth pressure boxes to test the changes in earth pressure at the sides of the structure (Figure 8). All earth pressure boxes were placed 10 cm from the surface of utility tunnel. A total of 98 earth pressure boxes were used to test the earth pressure under the action of different values of vertical dislocation s (s = 9, 19, 30, 40, 50, 60, 70, and 80 mm).

The differential settlement displacement of the model structure was measured with displacement meters. At the intersection of the structure and the ground fissure, which is 0.08 m on each side, a total of three measuring sections and 24 displacement meters are used to measure the differential settlement of the utility tunnel structure (Figure 9).

3. Test Results and Analysis

3.1. Earth Pressure
3.1.1. Longitudinal Earth Pressure Variations

As shown in Figure 10(a), the vertical contact with the earth pressure along the bottom of the utility tunnel was mainly manifested by a small amount of change in the hanging wall when the vertical settlement of the ground fissure increased; however, the footwall position markedly changed during this process. The earth pressure reached its maximum value at 0.8 m from the footwall to the preset ground fissure and decreased as settlement increased. This may have been due to the emergence of the void area, where the section of the utility tunnel located in the footwall warped. With increased displacement level, the earth pressure on the hanging wall, except for the structure end, decreased significantly to 0. This was roughly consistent with the scope of the void area at the structure’s bottom, which was observed at the test site. The soil pressure of the footwall increased significantly, and the range of the hanging wall soil pressure decreased to 0 at 0 to 0.8 m (actual prototype hanging wall at 12 m). The footwall earth pressure increased within the range of 0–0.8 m (actual prototype lower plate at 12 m). At the 0.8 m measuring point of the hanging wall, when the settlement s was from 3 to 4 cm, the contact earth pressure was reduced to 0, which indicated that a void area had begun to appear at the bottom of the structure at this time.

As shown in Figure 10(b), the top of the utility tunnel earth pressure increased significantly on the hanging wall. The earth pressure decreased near the ground fissure at the top of utility tunnel; however, there was little change as the settlement increased. The earth pressure on both sides of the ground fissure decreased as settlement increased, which may be attributable to the influence of the void area. With increased s, the top contact earth pressure showed a significant increase at the hanging wall and significant decrease at the footwall. The increased range of the hanging wall at 0.3–1.5 m (the prototype within the range of 22.5 m) and decreased range of the footwall at 0.3–0.8 m (the prototype within the range of 12 m) were basically consistent with changes in the contact pressure at the structure’s bottom. This was roughly consistent with the main deformation zone of ground fissures mentioned in the specification, with the hanging wall at 0–20 m and footwall at 0–12 mm [29]. When the settlement was increased from 9 to 19 mm, the earth pressure at the structure’s top changed greatly, indicating that the structure was relatively stressed during this process.

3.1.2. Transverse Earth Pressure Variations

Transverse earth pressure variations on the top of the structure are shown in Figure 11. In Figure 11(a), this section is located from the intersection of the ground fissure and the axis of the utility tunnel structure to the hanging wall at 0.8 m. On the footwall, the earth pressure decreased as ground fissure vertical displacement increased. On the hanging wall, the earth pressure increased as ground fissure vertical displacement increased, forming a clockwise torque or “twist.” The position of the axis at the top of the structure bore the maximum earth pressure, but the earth pressure on both sides decreased. The twisting also loosened the soil on both sides of the structure.

In Figure 11(b), the section located from the intersection of the ground fissure and the axis of the utility tunnel structure to the footwall is 0.8 m. The axial line at the top of the structure bore the maximum earth pressure. On the hanging wall, the earth pressure increased as ground pressure vertical displacement increased; on the footwall, the earth pressure decreased as ground pressure vertical displacement increased. This is similar to the earth pressure behavior observed at the section from the intersection of the ground fissure and the axis of the utility tunnel structure to the hanging wall (also 0.8 m).

Transverse earth pressure variations on the bottom of the structure are shown in Figure 12. In Figure 12(a), the bottom of the structure under earth pressure extends from the intersection of the ground fissure and the axis of the utility tunnel structure to the hanging wall at 0.8 m. Earth pressure increased during the experiment on both the foot and hanging wall. The position of the axis at the top of the structure bore the maximum earth pressure, but the earth pressure on both sides decreased. The torsion of the structure loosened the soil on both sides of the structure.

The earth pressure at the same position at the top of the structure behaved similarly. In Figure 12(b), this section extends from the intersection of the ground fissure and the axis of the utility tunnel structure to the footwall (0.8 m). The axial line at the bottom of the structure bore the minimum earth pressure. On the footwall, the earth pressure decreased as ground fissure vertical displacement increased. On the hanging wall, the earth pressure first decreased and then increased over the course of the same increase in ground fissure vertical displacement.

3.1.3. Lateral Earth Pressure Variations

As shown in Figure 13(a), the earth pressure on the north side wall of the structure on the hanging and footwall decreased as ground fissure vertical displacement increased. The contact earth pressure between the north side of the structure and the soil reached the maximum value 0.032 MPa at the end of the footwall. The earth pressure at the ground fissure location reached the minimum value 0 MPa. Due to the presence of the void area, structure lateral earth pressure formed a clockwise torque; the structure twisted clockwise and the earth pressure decreased as ground fissure vertical displacement increased.

As shown in Figure 13(b), the contact earth pressure between the south side of the structure and the soil decreased at both the hanging wall and the footwall as ground fissure vertical displacement increased. The earth pressure at the ground fissure location reached the maximum value 0.02 MPa; it is very different from the north side of the structure. Except the variation at the ground fissure location, these variations (on the hanging wall and the footwall) in earth pressure are similar to those on the north side of the structure due to the clockwise twist of the structure.

3.2. Longitudinal Deformation of Steel

Figures 14 and 15 show the strain curves of the longitudinal structure bottom and top steel strain under various dislocations of the ground fissure. In this paper, the strain value is positive in tension and negative in compression. As shown in Figure 14, the bottom of the steel strain along the longitudinal direction at the end of the hanging wall transformed from tension to compression over the course of the experiment; a similar transformation occurred at the end of the footwall and near the ground fissure. Compression strain is generated at the end of the structure located on the footwall. The tensile strain at the footwall of the structure was higher than that at the hanging wall, and at 0.325 m from the ground fissure to the footwall, the tensile strain maximized.

As shown in Figure 15, the top of the steel strain along the longitudinal direction at the hanging wall and footwall was mainly in a state of tension. When the settlement reached 60 mm, the tensile strain reached yield, as the top of the concrete in the footwall cracked; this is why the s = 60 mm curve appears more above than s = 70 mm and s = 80 mm.

3.3. Longitudinal Deformation of Structure

Figures 16 and 17 show longitudinal strain curves of the top and bottom of the structural concrete surface under various dislocations of the ground fissure. As shown in Figure 16, the compression zone of the structure top was mainly distributed in the footwall; the tension zone of the structure top was mainly distributed in the hanging wall. This is mainly due to the structure being deformed by torsion. At a distance of 1.0 m from the ground fissure to the footwall, the compressive strain was concentrated and the concrete reached the yield when the ground fissure settlement reached 60 mm because the corresponding compressive strain became smaller after settlements of 70 and 80 mm. At the intersection of the structural axis and ground fissure, the strain changed from compression to tension and the force was more complicated.

As shown in Figure 17, the strain in the top of structure was mainly characterized by tension. At a distance of 1.0 m from the ground fissure to the footwall, the tension strain was concentrated and the concrete reached the yield when the ground fissure settlement reached 60 mm because the corresponding tension strain became smaller after settlements of 70 and 80 mm. When the settlement reached 60 mm, as the top of the concrete cracked in the footwall and the tensile strain was released, this is why the s = 60 mm curve appears more above than s = 70 mm and s = 80 mm. This is consistent with the results shown in Figure 15.

3.4. Convergence Deformation Law of Structure

Section 1 convergence deformation is shown in Figures 18 and 19. In this paper, the structure is convergence deformation, tension is positive, and compression is negative. As the vertical settlement increased, the displacement of the hanging wall of the utility tunnel changed gradually downward and rightward. The vertical displacement exceeded the rightward displacement and the vertical displacement of cabin 2 was greater than that of cabin 1. When the ground fissure settlement is from 9 mm to 19 mm, the cross-sectional displacement increases significantly.

The overall displacement of the structural section is asymmetric.

Section 2 convergence deformation is shown in Figures 20 and 21, where the section is located at the intersection of the ground fissure and the axis of the utility tunnel structure. Cabin 1 is in the footwall and cabin 2 is in the hanging wall. The cross-sectional displacement of the utility tunnel grew asymmetrical as the ground fissure vertical settlement increased; cabin 1 experienced significant upward displacement, while cabin 2 underwent significant downward displacement. The amount of displacement of the two was roughly the same.

Section 3 convergence deformation is shown in Figures 22 and 23. The cross-sectional displacement at the footwall of the utility tunnel was smaller than that of the hanging wall. Cabin 1 underwent upward displacement, while cabin 2 showed no significant changes. Cabin 1 displacement first increased as ground fissure vertical displacement increased. When the settlement of hanging wall is from 19 mm to 30 mm, the vertical displacement then began to increase consistently with the time and location of cracks on the soil surface.

According to the deformation diagram of each section shown in Figures 1823, it appears that the utility tunnel twisted in a clockwise direction. This is evident from the hanging wall to the footwall along the axis of the structure (Figure 24).

The twisting of the structure can be attributed to the presence of a void zone at the bottom of the utility tunnel structure (Figure 25). The overburden soil pressure within the structural void area is equivalent to a concentrated force P (Figure 26). Force P is concentrated on the centroid O of triangle ABC; the centroid of the triangle has an eccentricity e to the axis of the structure, external torque appears near the void area, and the structure twists under the action of torque. The falling of the footwall caused the structure to experience torsional deformation rather than only bending deformation. The circumferential shear flow in this section of the structure also indicates that it twisted clockwise (Figure 27). However, the direction of the shear stress at some points changed, which indicated that the structural stress field was changing due to the effects of ground fissures, which were similar to previous conclusions of a subway tunnel passing obliquely through a ground fissure [24].

4. Conclusions

A model test was performed in this study to assess the mechanical behavior of a utility tunnel crossing a ground fissure. The earth pressure, stress–strain relationship of the structure, and the structural displacement at various locations in the model structure were measured. The conclusions can be summarized as follows.(1)With increased hanging wall settlement, the vertical contact soil pressure between the soil and structure top showed a significant increase in the hanging wall and significant decrease in the footwall. With increased displacement level, the vertical contact earth pressure between the soil and structure bottom on the hanging wall, except for the structure end, decreased significantly to 0. This was roughly consistent with the scope of the void area at the structure’s bottom, which was observed at the test site. The transverse earth pressure at the top of the structure, which is at the position of the structural axis, was larger and significantly increased, with the earth pressure on both sides being smaller, and the earth pressure at the footwall gradually decreased. Also, the earth pressure at the hanging wall did not change much, forming a clockwise torque, and the structure was subject to torsional deformation.(2)The largest steel strain occurred in the footwall, either at the top or the bottom of the structure. Longitudinal steel strain affects the bottom of the structure not by bending but by torsional deformation. The strain of structural concrete surface reaches its maximum value in the footwall, as does the steel strain.(3)As per the observable structure displacement, the utility tunnel is twisted clockwise from the hanging wall to the footwall along the axis of the structure.(4)Based on the analysis of structural strain, earth pressure, and displacement, the structure is not only destroyed by bending deformation but also by torsional deformation. Structural deformation is mainly concentrated in the footwall. It is recommended to tailor structural designs to adapt to the various types of deformation caused by ground fissures, for example, by equipping parts of the structure passing through the ground fissure with flexible joints.

Data Availability

All data generated or analyzed during this study are included in the article.

Disclosure

This manuscript is the authors’ original work and has not been published nor has it been submitted simultaneously elsewhere.

Conflicts of Interest

The authors declare that they have no conflicts of interest.

Acknowledgments

The authors acknowledge the Key Research and Development Program of Shaanxi Province as the work described in this article is part of a research project on the “Seismic Response and Seismic Mitigation Measures for Utility Tunnel Structure under Trans-Ground Fissure” funded by them under Grant no. 2017ZDXM-SF–095. Also, the National Natural Science Foundation of China is acknowledged for funding under Grant no. 41877285 as the work described in this article is part of a research project on the “The Formation Mechanism and Evolution Process of Passive Soil-Arch Effect in front of Cantilever Rectangular Anti-Slide Piles in Loess Area.”