Abstract

The objective of this study is to examine the performance of the shallow reinforced concrete foundation of a large-scale wind turbine under the influence of environmental loads. A 2 MW horizontal-axis onshore wind turbine supported by a shallow concrete foundation was considered. The foundation stresses, foundation settlements, and static and dynamic contact pressures at various positions of the shallow foundation were monitored from the construction phase to the operation phase in the field. Numerical simulations were also performed to further analyze the behavior of the wind turbine foundation in different cases. The results demonstrate that the responses of the reinforced concrete foundation, i.e., foundation stresses, contact pressures, and foundation settlements, were variables closely related to the wind direction and wind speed. The distribution of foundation stresses suggested that a reasonable design of steel reinforcement cages around the foundation steel ring is important. The dynamic contact pressure of the foundation could reach 5 kPa, so the influence of dynamic wind loads on the foundation response could not be always neglected, particularly for the foundations seated on weak soils. The foundation settlement during the operation phase could be characterized by the logistic model, but its distribution was uneven due to the presence of eccentric upper weight and wind load. The findings would provide guidance for the foundation design of onshore wind turbines in hilly areas.

1. Introduction

As a clean, safe, and sustainable natural source, wind energy becomes increasingly important in power supply [13]. Plenty of new wind farms have been installed in mountainous and hilly regions in many countries as a strategy for narrowing the regional energy disparity [4, 5]. For instance, from 2016 to 2020, China has built 42,000 MW wind turbines in its central eastern and southern regions [6, 7], where there are mainly hilly, plateau, and mountainous terrains. Wind turbines therein are usually supported by large-scale shallow foundations lied on the strongly weathered rock, karst, or residual soils. Unlike building structures, dynamic wind loads are the main forces for a wind turbine, which could produce considerable vibrations and increased stresses, strains, and deformations in the structure, foundation, and subsoil [810]. Therefore, the shallow foundation of a wind turbine in mountainous and hilly regions must show satisfactory performances in resisting large wind loads.

To date, various methods have been applied to analyze the responses of shallow foundations [1113]. Al-Homoud and Al-Maaitah [14] carried out forced vertical vibration tests on shallow foundations resting on sand. The authors reported that the natural frequency increases while the vibration amplitude declines as the embedment depth, degree of saturation, and foundation base area increase. EI Sawwaf and Nazir [15] performed model tests on strip foundations supported on a loose sandy slope under both monotonic and cyclic loads. Their results indicated that the inclusion of soil reinforcement in the replaced sand not only significantly increases the stability of the sandy slope itself but also decreases much both the monotonic and cumulative cyclic settlements. Pasten et al. [16] developed a numerical method to analyze dynamic responses under repetitive vertical loads. It was found that the vertical settlement, horizontal displacement, foundation rotation, and stress redistribution within the soil mass change with increasing number of load cycles. Moreover, the displacement and rotation become more pronounced as the cyclic load amplitude increases. Chen et al. [17] conducted dimensionless parametric analyses to evaluate the dynamic responses of soil-foundation systems subjected to harmonic horizontal forces and rocking moments. Panique Lazcano et al. [18] proposed a pore-water pressure generation equation and evaluated the influence of pore pressure in the calculation of bearing capacity of shallow foundation on cohesive soil. The formulation is able to calculate the maximum cyclic load that a cohesive soil can resist before failure. Fattah et al. [19] examined the distribution of contact pressures under a circular shallow foundation subjected to vertical and rocking vibrations. It was found that the shallow foundation tends to have escalated stress distribution in the direction of rocking vibration to reach a peak at the center followed by a gentle drop.

Nevertheless, only a few related works have been reported in the field of wind turbines [3, 4]. The work of Harte et al. [20] and Taddei et al. [21] stated that the soil-structure interaction plays an important role in the performance of wind turbine shallow foundations. Madaschi et al. [22] examined the dynamic behavior of the shallow foundation of a small full-scale wind turbine. It was noted that the vibration of the wind turbine tower induces a sort of forced, damped harmonic excitation in the foundation. More recently, Gao et al. [9] and Deng et al. [23] conducted numerical simulations and physical model tests on a 2 MW wind turbine subjected to random wind loads. The authors demonstrated that the surrounding environment of the wind turbine foundation is affected by dynamic wind loads, and the dynamic amplification factors strongly depend on the wind speed and spatial position. However, the previous work did not concern the behavior of wind turbine foundation itself in the construction phase. Using numerical methods, Pham et al. [24] analyzed the responses of the shallow foundation of an onshore wind turbine resting on natural or improved ground. They stated that the soil settlement and the foundation rotation decrease when the area improvement ratio increases; meanwhile, the presence of the overturning moment on the raft increases the total and differential soil settlements. Wang and Ishihara [25] developed a dynamic Winkler model for the dynamic response analysis of shallow foundation supported wind turbines. It was found that without considering the foundation uplift, the moment on the wind turbine tower is slightly overestimated, while that on the shallow foundation is significantly underestimated for the large soil stiffness. He et al. [10] conducted structural health monitoring of a 1.5 MW onshore wind turbine foundation with embedded ring. The authors reported that the long-term monitoring of the local concrete deformation is necessary to ensure the safety of the foundation, but their work mainly focused on the performance of embedded rings.

The purpose of the current study is to investigate the performance of wind turbine foundations under environmental loads. A common 2 MW horizontal-axis wind turbine supported by a shallow concrete foundation was considered. The foundation stresses, foundation settlements, static contact pressures, and dynamic contact pressures at various positions of the shallow foundation of this type of wind turbine were collected from a wind farm in China. Numerical simulations were also conducted to further examine the performance of the wind turbine foundation. The monitored data and calculated results were analyzed and compared. The findings obtained from this study would provide guidance for the design of wind turbine foundations in hilly and mountainous areas.

2. Engineering Background

The Qiaoshi wind farm (25°29′06.4″ N, 112°40′16.7″ E) is located in Guiyang County, Chenzhou City, China (Figure 1). This region is a subtropical monsoon climate, with abundant rainfall and distinctive seasons. Over the past 40 years, the average annual temperature is 17.2°C, the average annual wind speed is 2.04 m/s, and the maximum average annual wind speed is 2.65 m/s. The prevailing wind direction is from the north-northeast (NNE) and south (S), among which the NNE direction has the largest frequency of about 15%. The elevation of the Qiaoshi wind farm is 400–600 m, and the landscape is characterized by low hills with mean slopes of 15°–30°. The natural surface of the ground is covered by low shrubs. The ground is extensively covered with quaternary residual soils, and the bedrocks mainly include granite porphyry, limestone, sandstone, and dolomite. Dozens of 2 MW horizontal-axis wind turbines (XEMC Windpower Company, China) have been installed on this wind farm. The specification of the wind turbine is shown in Table 1. All wind turbines were installed on hill tops or ridges and supported by circular spread foundations made of reinforced concrete. The external diameters and the embedment depths of the foundations were 18.4 m and 3.1 m, respectively.

A representative wind turbine on the Qiaoshi wind farm was investigated. The wind turbine was supported by a circular spread concrete foundation that was situated on a hillside. The physical and mechanical properties of the subsoil and bedrock are shown in Table 2.

3. Study Methods

3.1. Field Monitoring

The monitored items included the foundation stress, the foundation settlement, and the static and dynamic contact pressures between the foundation and the subsoil, which are important indicators to evaluate the performance of a shallow foundation.

The axial stresses of many steel bars in different positions and directions of the shallow foundation were monitored by stress gauges (see Figure 2). On the one hand, 32 stress gauges labeled SG-V1-0°∼335°, SG-V2-0°∼335°, SG-V3-0°∼335° and SG-V4-0°∼335° were set to measure the axial stresses of the vertical steel bars in the foundation. On the other hand, another 32 stress gauges (i.e., SG-B1-0°∼335°, SG-B2-0°∼335°, SG-T1-0°∼335°, and SG-T2-0°∼335°) were used to acquire the axial stresses of the radial steel bars near the foundation bottom and top surfaces in eight directions. The axis direction of each cylinder marking in Figure 2 represents the test direction of a stress gauge. Note that the 0° direction represents the prevailing wind direction in this study. The stress gauges had a measurement range of −200 MPa–350 MPa, a sensitivity of 0.1 MPa, and a precision of 0.2% FS.

The geometric leveling method was used to observe the settlements of the wind turbine foundation. Four observation marks (i.e., SM-0°∼270°) were fixed on the foundation edge in different directions, as shown in Figure 3. The benchmark was positioned on the exposed bedrock near the foundation. During the observation, closed leveling lines were established from the benchmarks and passing each observation mark. The closing error of the leveling line must be less than (L is the distance).

Static Earth pressure cells were employed to monitor the static contact pressures between the foundation and the subsoil [26]. The Earth pressure cells were circular with 118 mm in diameter and 30 mm in thickness. The Earth pressure cells had a measurement range of 0.6 MPa, a sensitivity of 0.1 kPa, and a precision of 0.1% FS. Their locations are illustrated in Figure 4. One Earth pressure cell (i.e., PC0-0°) was installed in the center of the foundation bottom, eight Earth pressure cells (i.e., PC1-0°∼315°) were placed in eight directions at a radius of 3 m, and another eight Earth pressure cells (i.e., PC2-0°∼315°) were installed in eight directions at a radius of 6 m. Static Earth pressure cells were also used to measure the static contact pressures between the lateral surface of the foundation and the backfill. Four Earth pressure cells (i.e., PC-S-0°∼270°) were fixed in four directions at a shallow depth, and another four Earth pressure cells (i.e., PC-D-0°∼270°) were installed in four directions at a deeper position. In addition, the dynamic contact pressures of the wind turbine foundation were monitored using four dynamic Earth pressure cells (i.e., DPC-0°∼270°) with a range of 0.8 MPa and a precision of 0.1 kPa.

The field monitoring started at the beginning of the construction phase of the foundation and lasted to the operation phase of the wind turbine. Some important time points of the construction and operation phases are listed in Table 3.

4. Numerical Simulation

A three-dimensional numerical model of the wind turbine foundation is created using the finite element software ABAQUS, as shown in Figure 5. The model basically consists of the foundation (the steel ring, the steel reinforcement cage, and concrete) and the subsoil (diameter = 80 m, height = 30 m). The dimension of the foundation model is the same as that of the foundation of the monitored wind turbine on the Qiaoshi wind farm. For simplicity, the subsoil is regarded to be a single layer of residual soils. This simplification will not greatly affect the numerical results since this study mainly focuses on the response of the foundation rather than the behavior of the subsoil. The concrete and steel are modeled as isotropic elastic materials, and the subsoil is modeled using the Mohr-Coulomb model. The material properties used in the simulation are given in Table 4. The used soil properties are failing into the ranges of measured data shown in Table 2. The properties of the steel and concrete are determined referring to relevant Chinese specifications [27, 28]. The steel reinforcement cage is simulated by beam elements (B31), while the remaining parts (i.e., concrete, subsoil, and steel ring) are simulated by solid elements (C3D10). [29] The element size is determined after convergence analysis considering the calculation accuracy and computation cost. The whole finite element model contains 63895 elements and 56941 nodes in total.

The steel reinforcement cage is linked to the concrete using the embedded technique [30]. Coulomb's friction law with a friction coefficient of 0.35 is applied to simulate the tangential behavior between the foundation and the subsoil [4, 9]. The contact in the normal direction at the interface between the foundation and the subsoil is considered to be a hard contact. The mesh tie constraint provided in ABAQUS is adopted to connect the concrete to the steel ring. The bottom boundary of the model is fully fixed in both the vertical and horizontal directions, and the lateral boundary of the finite element model is fixed in the horizontal direction. Two cases (i.e., and ) with wind speeds of 12 m/s and 14 m/s at the hub height are considered in simulations to compare with the monitored results. The loads transmitted from the superstructure to the foundation top are simplified into a horizontal load, a vertical load, and a moment rotating around a horizontal axis [3]. The loads shown in Table 5 are calculated using the GH Bladed software, which is a commercial software widely used in wind turbine design and analysis.

5. Results and Discussion

5.1. Foundation Stress

Figure 6 illustrates the simulated axial stress contours of the entire steel reinforcement cage of the foundation in difference cases. It is observed that in both cases (i.e., and ) the axial stresses of the steel reinforcement cage were in the range of −10 MPa–5 MPa, which were far less than the strengths of the steel. Moreover, the part on the downwind side likely undergone compressive stress while that on the upwind side generally withstood tensile stress. Compared with the circumferential steel bars, the radial steel bars and vertical steel bars suffer higher stresses. Both the maximum compressive stress and tensile stress appeared in the vertical steel bars near the foundation steel ring. It suggests that a reasonable design of the steel reinforcement cage around the foundation steel ring is critical for the safety of the shallow foundation of a wind turbine [10].

Figures 7 and 8 compare the axial stresses of steel bars in the foundation obtained by field monitoring and numerical simulations. It is noted that some of the vertical steel bars (e.g., SG-V2-90°, 135°, 180°, 225° in Case ) were in tension while the others (e.g., SG-V2-270°, 315°, 0°, 45° in Case ) were in compression. Furthermore, the axial stresses of the vertical steel bars were obviously affected by the wind speed. Generally, the larger the wind speed was, the larger the horizontal wind load and moment applied to the wind turbine were, and thus the larger the tensile stresses or compressive stresses of the vertical steel bars were. The vertical steel bars at SG-V3 and SG-V4 mainly suffered compressive stresses. The radial steel bars near the foundation top surface (i.e., at SG-T1 and SG-T2) were mainly in compression while the radial steel bars on the foundation bottom (i.e., at SG-B1 and SG-B2) were mainly in tension. Overall, both the simulated and monitored results showed similar variations and distributions although the values were not exactly the same. This is reasonable because some simplifications or assumptions are made to the materials and loads in numerical simulations. Hence, the numerical model is considered to be capable of characterizing the behavior of the wind turbine foundation for engineering purposes.

5.2. Static Contact Pressure

Figure 9 presents the time histories of the monitored static contact pressures on the foundation bottom. It is observed that the static contact pressures at various monitoring points considerably went up during the foundation construction and backfilling process (i.e., t = 0–35 d). As the superstructure (i.e., tower, nacelle, and rotor) was gradually installed on the foundation (i.e., t = 68–86 d), the distribution of static contact pressures gradually slightly varied from homogeneous to uneven due to the eccentricity of the weight of wind turbine superstructure. During the operation of the wind turbine (i.e., t > 103 d), large wind loads were applied to the superstructure of the wind turbine; this led to an obvious variation of the static contact pressure. In this process, the direction of the monitoring point where the static contact pressure was the maximum changed with the change in wind direction. Furthermore, one can note that the static contact pressures at PC2 were generally smaller than those at PC1. The static contact pressures on the upwind side were smaller than those monitored on the downwind side, which is in line with the axial stresses of steel bars on the foundation bottom.

Figure 10 illustrates the simulated contours of static contact pressures on the foundation bottom in two different cases (i.e., and ). It is observed that the static contact pressure was not homogeneously distributed but exhibited large values on the downwind side and relatively small values on the upwind side. This finding is broadly in agreement with the monitored results and those reported in the literature [9]. The abnormal contact pressures at individual points in Case appear due to stress concentrations when the eccentricity of the foundation is relatively small. Figure 11 compares the simulated static contact pressures with those monitored in the field. Obviously, the simulated data and the monitored values were not precisely consistent. But, as expected, the simulated and monitored static contact pressures showed similar distributions. Additionally, one can note that the distribution of static contact pressures on the foundation bottom was affected by the wind speed. For example, the static contact pressures monitored on t = 117 d with a hub wind speed of 12 m/s were quite different from those monitored on t = 200 d with a hub wind speed of about 14 m/s.

Figure 12 presents the time histories of the monitored static contact pressures on the lateral side of the foundation. As expected, the static lateral contact pressures at a smaller depth (i.e., PC-S) were smaller than those at a larger depth (i.e., PC-D). Generally, the static lateral contact pressures of the foundation showed a similar variation trend as the static contact pressures on the foundation bottom during the process of foundation construction and backfilling (see Figure 9). In this process, the static lateral contact pressures considerably increased from zero up to around 13 kPa at PC-S and 34 kPa at PC-D, respectively. Afterward, the static lateral contact pressures exhibited great fluctuations during the installation of the superstructure of the wind turbine and relatively small fluctuations during the operation phase. As a whole, the static contact pressures on the lateral side of the foundation are several times smaller than those on the bottom.

6. Foundation Settlement

Figure 13 shows the time histories of the foundation settlements from the backfilling phase to the operation phase. It is noted that the foundation settlements slightly increased when the foundation pit was backfilled (i.e., t = 35–68 d). During the installation of the superstructure of the wind turbine (i.e., t = 68–86 d), the foundation settlement showed a significant increase in a step-like manner. This is because the tower sections, nacelle, and wind rotor were installed successively. One can also note a slight wave of the curve in this process; this is likely due to the movement of wheel cranes and transport vehicles. Moreover, because of the eccentricity of the upper weights and the existence of wind loads, the foundation settlements at different positions were different. The foundation settlements were then stabilized during the period between t = 86 d and t = 103 d. As the operation of the wind turbine was started (i.e., t > 103 d), the foundation settlements increased with a decreasing rate. Three months later, the foundation settlements reached the equilibrium. After the equilibrium, the maximum foundation settlement was about 15.0 mm at SM-180°, and the minimum foundation settlement was 8.6 mm at SM-0°. The differential settlement was (15.0–8.6) mm/7.5 m = 0.85 mm/m, which is in the range of allowable value [31]. This indicates that the wind turbine foundation was stable.

The variation of foundation settlements during the operation can be described by the logistic model, which has the following form:where s is the settlement of the wind turbine foundation; t is the time; a is the instant settlement rate; K is the final settlement; c is a constant.

The fitting parameters of two example curves are summarized in Table 6. It shows that the logistic model can well characterize the settlement evolution of the wind turbine foundation.

Figure 14 depicts the simulated contour of the foundation settlement. One can note that the foundation settlement showed an uneven distribution. The simulated settlements of the foundation baseplate varied from 20.0 mm to 25.6 mm in Case and from 19.0 mm to 26.9 mm in Case . The simulated foundation settlements were nearly twice the monitored results, but they had the same order of magnitude. The numerical work of Gao et al. [9] showed that the maximum settlement at a hub wind speed of 11 m/s is about 3.5 mm, occurring near the downwind edge of the foundation. Obviously, the previous results are close to those of the current study.

6.1. Dynamic Contact Pressure

Figure 15 presents the time histories of the dynamic (i.e., fluctuating) contact pressures in Case . It is noted that the maximum dynamic contact pressure was 3.59 kPa at DPC-0°. Since DPC-0° was located between PC1-0° and PC2-0° (Figure 11), the static contact pressure at DPC-0° is assumed to be the average value of the static contact pressures at PC1-0° and PC2-0°. The estimated static contact pressure at DPC-0° was about 61.75 kPa, so the dynamic amplification factor at DPC-0° was 3.59/61.75 = 5.8%. Since the maximum dynamic contact pressure at DPC-180° was 5.73 kPa and the static contact pressure at DPC-180° was about 84.75 kPa, the dynamic amplification factor at DPC-180° was 5.73/84.75 = 6.8%. Similarly, it is derived that maximum dynamic contact pressure was 0.79 kPa and the dynamic amplification factor was 1.2% at DPC-90°; the maximum dynamic contact pressure was 0.62 kPa and the dynamic amplification factor was 1.0% at DPC-270°. These findings were roughly in agreement with those reported by Deng et al. [23], indicating that the wind load had a dynamic effect on the contact pressures of the wind turbine foundation.

7. Conclusions

This paper presented a case study of the reinforced concrete foundation of a large-scale wind turbine on the Qiaoshi wind farm in China. The foundation stresses, foundation settlements, static contact pressures, and dynamic contact pressures of the foundation at various positions were monitored and simulated. The following conclusions can be drawn:(1)Radial steel bars in the foundation baseplate mainly underwent tensile stress while those near the top surface of the foundation mainly suffered from compressive stress. The stresses of the vertical steel bars were either compressive or tensile depending on the position. However, the stresses of all steel bars were far less than the tensile or compressive strength of the steel.(2)The contact pressures on the bottom of the reinforced concrete foundation were variables that are highly dependent on the wind direction and wind speed. The dynamic contact pressure of the foundation could reach 5 kPa, indicating that the influence of dynamic wind loads on the performance of the reinforced concrete foundation should not be always neglected, particularly for the foundations seated on weak soils.(3)The settlement of the wind turbine foundation was uneven due to the presence of eccentric upper weight and wind load. The monitored settlement values were usually in the range of 0–20 mm from the foundation backfilling phase to the operation phase. The evolution of foundation settlement during the operation phase could be characterized by the logistic model.(4)A reasonable design of the steel reinforcement cage around the foundation steel ring is critical for the safety of the reinforced concrete foundation of wind turbines. Meanwhile, the wind-induced dynamic effect also needs to be taken into consideration in the design of wind turbine foundations although the effect may be not obvious in regular cases.

Data Availability

Because the data in the paper are still a project of the National Natural Science Foundation of China, the data need to be used in the follow-up study of the project. So, all the figures and tables data used to support the findings of this study were supplied by the corresponding author under license and so cannot be made freely available. Requests for access to these data should be made to Zongwei Deng, Hunan City University, No. 518, Yingbin East Road, 413000, YiYang, Hunan, China (tel:086–13973760738; e-mail: dengzongwei@hncu.edu.cn).

Conflicts of Interest

The authors declare that they have no conflicts of interest.

Acknowledgments

This work was supported by the Postgraduate Research and Innovation Project of Hunan Province (CX20190657), the National Natural Science Foundation of China (51674041 and 51474103), the Natural Science Foundation of Hunan Province, China (2020JJ4156), and the Changsha Municipal Natural Science Foundation (kq2014110).