[Retracted] Study on Thermal Performance Measurement and Construction of Passive Exterior Wall with Low Energy: Teaching and Laboratory Building of Shandong Jianzhu University

Table 1

Physical property parameters of building materials for the test external wall.

IDStructural layerHeat conductivity coefficient (w·m−1·K−1)Thickness (mm)Water vapor penetration coefficient, (ng·Pa−1 m−1·s−1)Sensor ID

1Coating material of interior wall
2M7.5 cement mortar0.93155.81
3Steam aerated concrete slab0.14620027.72
4M7.5 cement mortar0.93105.83
5Graphite polystyrene plate0.0321004.5
6Adhesive mortar0.9355.84
7Graphite polystyrene plate0.0321004.5
8Anticrack mortar0.9355.85
9Fluorocarbon lacquer paint of exterior wall0.1 mL

According to the test method of JG/T210-2007 “Primer for Building Internal and External Walls,” the water permeability test result of the alkali resistant sealing primer for the external wall coating of this project is 0.1 ml, and the water resistance test result is 96 h without abnormality. Water vapor permeability coefficient refers to the water vapor partial pressure difference on both sides of a material with a thickness of 1 m under stable penetration conditions of 1 Pa, within 1 hour (the amount of water vapour that penetrates through an area of 1 square meter).