Research Article

A New Type of Air Conditioning System Based on Finned Ceiling Radiant Coupled with Independent Fresh Air and Its Thermal Comfort Experimental Study

Table 5

Moisture content of outdoor air and indoor fresh air.

Three kinds of working conditionAir samplesAverage temperature (°C)Average relative humidity (%)Moisture content (g/kg)Dehumidification efficiency (%)

Dehumidification in transition season (20°C∼22°C)Air from the indoor air outlet13.656.805.4851.6
Outdoor air21.570.6911.33

Ordinary refrigeration (31°C∼33°C)Air from the indoor air outlet18.467.58.961.2
Outdoor air32.274.822.91

High-temperature cooling (37°C∼39°C)Air from the indoor air outlet18.672.19.6370.4
Outdoor air37.578.232.6