Research Article
A New Type of Air Conditioning System Based on Finned Ceiling Radiant Coupled with Independent Fresh Air and Its Thermal Comfort Experimental Study
Table 5
Moisture content of outdoor air and indoor fresh air.
| Three kinds of working condition | Air samples | Average temperature (°C) | Average relative humidity (%) | Moisture content (g/kg) | Dehumidification efficiency (%) |
| Dehumidification in transition season (20°C∼22°C) | Air from the indoor air outlet | 13.6 | 56.80 | 5.48 | 51.6 | Outdoor air | 21.5 | 70.69 | 11.33 | |
| Ordinary refrigeration (31°C∼33°C) | Air from the indoor air outlet | 18.4 | 67.5 | 8.9 | 61.2 | Outdoor air | 32.2 | 74.8 | 22.91 | |
| High-temperature cooling (37°C∼39°C) | Air from the indoor air outlet | 18.6 | 72.1 | 9.63 | 70.4 | Outdoor air | 37.5 | 78.2 | 32.6 | |
|
|