Research Article

Coordinate Control of Power/Current for Grid-Connected Inverter Based on PCI Controller under Unbalanced Grid Conditions

Table 3

Control performance comparison of the coordinate control under different cases.

Case aCase bCase c
Control in Ref. [20]Proposed controlControl in Ref. [20]Proposed controlControl in Ref. [20]Proposed control

Current THD of phase-A (%)0.1 s~0.2 s3.751.594.652.374.823.35
0.2 s~0.4 s5.775.757.386.248.257.46
0.4 s~0.5 s10.627.0011.738.2624.8810.15

DC-link voltage ripple (%)0.470.210.210.180.510.27

Settling time (s)0.100.100.090.100.120.11

Overshoot of DC-link voltage (%)1.910.542.720.493.460.34

Amplitude of active power oscillations (% of P)28.1021.4828.9125.7140.9135.46

Amplitude of reactive power oscillations (% of P)23.1820.0822.8916.9939.7330.77