Coordinate Control of Power/Current for Grid-Connected Inverter Based on PCI Controller under Unbalanced Grid Conditions
Table 3
Control performance comparison of the coordinate control under different cases.
| | Case a | Case b | Case c | Control in Ref. [20] | Proposed control | Control in Ref. [20] | Proposed control | Control in Ref. [20] | Proposed control |
| Current THD of phase-A (%) | 0.1 s~0.2 s | 3.75 | 1.59 | 4.65 | 2.37 | 4.82 | 3.35 | 0.2 s~0.4 s | 5.77 | 5.75 | 7.38 | 6.24 | 8.25 | 7.46 | 0.4 s~0.5 s | 10.62 | 7.00 | 11.73 | 8.26 | 24.88 | 10.15 |
| DC-link voltage ripple (%) | 0.47 | 0.21 | 0.21 | 0.18 | 0.51 | 0.27 |
| Settling time (s) | 0.10 | 0.10 | 0.09 | 0.10 | 0.12 | 0.11 |
| Overshoot of DC-link voltage (%) | 1.91 | 0.54 | 2.72 | 0.49 | 3.46 | 0.34 |
| Amplitude of active power oscillations (% of P) | 28.10 | 21.48 | 28.91 | 25.71 | 40.91 | 35.46 |
| Amplitude of reactive power oscillations (% of P) | 23.18 | 20.08 | 22.89 | 16.99 | 39.73 | 30.77 |
|
|