Research Article
Evaluating Fractional PID Control in a Nonlinear MIMO Model of a Hydroelectric Power Station
Table 1
Specification of step response for advanced control design at Dinorwig [
1,
3].
| Test | Specification for single unit operation. | Single unit response with the governor reported in [3]. | Single unit response with GS-AWU-PDF-FO. |
| P1 | P1 ≥ 90% at = 10s | 81% at 10s, | 94.6 % at 10 s, | 90% at 13.7 s | 90% at 8.3 s |
| P2 | P2 ≤ 5% and ≤ 20s | No overshoot | No overshoot |
| P3 | = 25s for P3 ≤ 1% | 25.9 s | 16.9 s |
| P4 | = 60s for P4 ≤ 0.5% | 29.2 s | 19.3 s |
| P5 | = 8s | 12.1 s | 7.64 s |
| P6 | P6 = 2% | 1.75% | 2% |
| P7 | = 1.5s | 0.88 s | 0.975 s |
|
|