Research Article

Analysis of the Influence of Renewable Generator Frequency Endurance Capability on Low-Frequency Load Shedding: A Hunan Case Study

Table 2

Allowable operation time of abnormal frequency.

Frequency range HzCumulative allowable running time minAllowable running time per time sec

51.0∼51.5>30>30
50.5∼51.0>180>180
48.5∼50.5Continuous operation
48.5∼48.0>300>300
48.0∼47.5>60>60
47.5∼47.0>10>20
47.0∼46.5>2>5