Analysis of the Influence of Renewable Generator Frequency Endurance Capability on Low-Frequency Load Shedding: A Hunan Case Study
Table 4
Statistical analysis results of frequency endurance capability.
| Round of actions | Foundation turn | Special turn | I | II | III | IV | V | I | II | III |
| Action frequency (Hz) | 49 | 48.75 | 48.5 | 48.25 | 48 | 49.25 | 49.25 | 49.25 | Action delay (s) | 0.15 | 0.15 | 0.15 | 0.15 | 0.15 | 10 | 15 | 20 | Load reduction ratio at each level (%) | 6.6 | 6.57 | 6.57 | 6.57 | 6.57 | 2.39 | 2.39 | 2.39 |
|
|