Research Article

Self-Adaptive Firefly-Algorithm-Based Unified Power Flow Controller Placement with Single Objectives

Table 3

Performance solutions of the IEEE 14 bus system.

 MethodPloss(MW)TVDMVSIVlow/Vhigh (p,u)

Before UPFC placement 13.36630.38220.07511.014/1.057

Case 1SAFA13.21120.56290.07501.005/1.045
HBA13.22200.46790.06511.009/1.040
BFA13.23690.52550.06200.990/1.041

Case 2SAFA15.72260.06030.09340.996/1.024
HBA15.72330.06570.09500.991/1.023
BFA15.55170.06940.10050.994/1.028

Case 3SAFA13.30660.49560.04881.016/1.073
HBA13.41550.47640.05121.019/1.069
BFA13.29300.46920.05381.023/1.068