Optimal Setting Method of Inverse Time Overcurrent Protection for the Distribution Networks Based on the Improved Grey Wolf Optimization
Table 4
Protection setting value when a two-phase short circuit occurs.
| Relay | Tp | Ip (A) |
| CB1 | 0.379 | 276.1 | CB2 | 0.301 | 193.2 | CB3 | 0.172 | 203.5 | CB4 | 0.099 | 104.7 | CB5 | 0.202 | 182.0 | CB6 | 0.108 | 106.9 | CB7 | 0.143 | 246.6 | CB8 | 0.101 | 113.7 | CB9 | 0.109 | 114.1 | CB10 | 0.203 | 232.5 | CB11 | 0.192 | 126.2 | CB12 | 0.105 | 103.9 | CB13 | 0.112 | 102.3 | CB14 | 0.097 | 101.9 |
|
|