Research Article
Optimal Setting Method of Inverse Time Overcurrent Protection for the Distribution Networks Based on the Improved Grey Wolf Optimization
Table 5
Protection action time when a two-phase short circuit occurs.
| Fault location | Action time of primary protection (s) | Action time of backup protection (s) |
| B1–B2 | 1.119 | — | B2–B3 | 1.027 | 1.539 | B3–B4 | 0.623 | 1.238 | B4–B5 | 0.326 | 0.879 | B2–B9 | 0.602 | 1.411 | B9–B10 | 0.310 | 0.851 | B2–B6 | 0.656 | 1.932 | B6–B7 | 0.344 | 0.909 | B6–B8 | 0.357 | 0.868 | B3–B11 | 0.832 | 1.376 | B11–B12 | 0.773 | 1.271 | B12–B13 | 0.446 | 0.958 | B4–B14 | 0.359 | 0.913 | B4–B15 | 0.307 | 0.826 |
|
|