A Comparison of Metaheuristic Techniques for Solving Optimal Sitting and Sizing Problems of Capacitor Banks to Reduce the Power Loss in Radial Distribution System Table 1 Results comparison of metaheuristic techniques on an IEEE-34 bus system.
Parameter Base case PSO [34 ] Harmonic search BAT Cuckoo Grey wolf Capacitor size and sitting (node) — 781 (19) 803 (22) 479 (20) 1000 (19) 800 (26) 650 (10) 1150 (25) 10 (650) 19 (850) 25 (700) 500(10) 500(25) 660 (19) 290 (22) Minimum voltage (node) 0.9423 (bus 27) — 0.9501 (27) 0.9500 (27) 0.9503 (27) 0.9507 (27) Maximum voltage (node) 1.00 (bus 1) — 1.00 (1) 1.00 (1) 1.00 (1) 1.00 (1) Real power loss (kW) 223.85 168.6 167.9468 165.3482 160.3 159.29 Reactive power loss (kVAR) 66.4783 49.9924 49.0422 49.9579 48.8243 47.8127 % P loss reduction — 24.6817 24.9735 26.1343 28.3895 28.84% % Q loss reduction — 24.7989 26.2282 24.8508 26.556 28.0777 kVAR injected — 2063 1800 1800 2200 1950 Computation time (s) 0.903117 17.809493 9.892012 2.005097 0.14682 0.43199 Net savings ($) — 18398 20635 21711 19194 20115