Research Article
A Unified Power Quality Conditioner for Feeder Reconfiguration and Setting to Minimize the Power Loss and Improve Voltage Profile
Table 1
The results of UPQC placement and reconfiguration simultaneously in 69-bus network.
| | Tie switches | UPQC characteristics | Total losses (KW) | Voltage deviation | Vmin (PU) | Vave (PU) | Line | Shunt power (MVAR) | Series power (MVAR) |
| Case 1 | 69, 70, 71, 72, 73 | - | - | - | 224.92 | 0.0265 | 0.9091 | 0.9734 | Case 2 | 12, 13, 58, 61, 69 | - | - | - | 99.88 | 0.0135 | 0.9427 | 0.9865 | Case 3 | 14, 58, 63, 69, 70 | 60 | 1.1 | 0.91 | 73.10 | 0.0112 | 0.9654 | 0.9887 | Case 4 | 10, 12, 18, 58, 61 | 73 | 1.49 | 1.031 | 150.72 | 0.0044 | 0.9688 | 0.9956 | Case 5 | 14, 58, 64, 69, 70 | 61 | 1.78 | 0.384 | 84.85 | 0.0082 | 0.9719 | 0.9917 |
|
|