A Communication-Assisted Distance Protection for AC Microgrids considering the Fault-Ride-Through Requirements of Distributed Generators

Table 1

Relay operating time (s) during a fault occurring at 87.5% of the feeder AB in the islanded mode.

ITA protection relaySimulation resultsCalculation results
L-GLLLL-GLLL
Fault resistance (Ω)Fault resistance (Ω)Fault resistance (Ω)Fault resistance (Ω)
0.01501000.015100.01501000.01510

Primary protection10.1510.1490.1460.1510.1520.1520.1410.1510.1510.1490.1490.1510.150
20.0010.0010.0010.0020.0020.0020.0020.0010.0010.0030.0010.0010.001

Backup protection10.5590.5720.5810.5600.5590.5620.5700.5610.5630.5890.5630.5650.581
20.5570.5580.5610.5570.5570.5570.5560.5570.5570.5590.5570.5570.557
40.6320.6140.6080.6340.6310.6260.6250.6260.6240.6000.6230.6210.607
80.7800.7120.6790.7790.7610.7490.8030.7500.7450.7230.7540.7420.775
90.7610.6540.6190.7130.7300.7410.7220.7410.7280.6030.7070.7170.776