A Communication-Assisted Distance Protection for AC Microgrids considering the Fault-Ride-Through Requirements of Distributed Generators
Table 2
Relay operating time (s) during a fault occurring at 12.5% of the feeder AB in the grid-connected mode.
| ITA protection relay | Simulation results | Calculation results | L-G | LL | LL-G | LLL | Fault resistance (Ω) | Fault resistance (Ω) | Fault resistance (Ω) | Fault resistance (Ω) | 0.01 | 50 | 100 | 0.01 | 5 | 10 | 0.01 | 50 | 100 | 0.01 | 5 | 10 |
| Primary protection | 1 | 0.001 | 0.001 | 0.001 | 0.001 | 0.001 | 0.001 | 0.001 | 0.001 | 0.001 | 0.001 | 0.001 | 0.001 | 0.001 | 2 | 0.150 | 0.153 | 0.156 | 0.151 | 0.151 | 0.152 | 0.149 | 0.151 | 0.151 | 0.149 | 0.149 | 0.151 | 0.150 |
| Backup protection | 1 | 0.542 | 0.544 | 0.547 | 0.541 | 0.542 | 0.542 | 0.541 | 0.541 | 0.541 | 0.541 | 0.542 | 0.543 | 0.541 | 2 | 0.572 | 0.571 | 0.571 | 0.573 | 0.572 | 0.574 | 0.572 | 0.571 | 0.576 | 0.572 | 0.572 | 0.574 | 0.573 | 4 | 0.796 | 0.711 | 0.676 | 0.800 | 0.772 | 0.752 | 0.799 | 0.800 | 0.800 | 0.806 | 0.773 | 0.753 | 0.774 | 8 | — | — | — | — | — | — | — | — | — | — | — | — | — | 9 | 0.822 | 0.736 | 0.698 | 0.782 | 0.762 | 0.746 | 0.812 | 0.783 | 0.782 | 0.777 | 0.766 | 0.750 | 0.778 |
|
|