Research Article

A Communication-Assisted Distance Protection for AC Microgrids considering the Fault-Ride-Through Requirements of Distributed Generators

Table 2

Relay operating time (s) during a fault occurring at 12.5% of the feeder AB in the grid-connected mode.

ITA protection relaySimulation resultsCalculation results
L-GLLLL-GLLL
Fault resistance (Ω)Fault resistance (Ω)Fault resistance (Ω)Fault resistance (Ω)
0.01501000.015100.01501000.01510

Primary protection10.0010.0010.0010.0010.0010.0010.0010.0010.0010.0010.0010.0010.001
20.1500.1530.1560.1510.1510.1520.1490.1510.1510.1490.1490.1510.150

Backup protection10.5420.5440.5470.5410.5420.5420.5410.5410.5410.5410.5420.5430.541
20.5720.5710.5710.5730.5720.5740.5720.5710.5760.5720.5720.5740.573
40.7960.7110.6760.8000.7720.7520.7990.8000.8000.8060.7730.7530.774
8
90.8220.7360.6980.7820.7620.7460.8120.7830.7820.7770.7660.7500.778