A Communication-Assisted Distance Protection for AC Microgrids considering the Fault-Ride-Through Requirements of Distributed Generators
Table 3
Relay operating time (s) during a fault occurring in the feeder AB in the islanded mode.
| Fault location | Fault resistance (Ω) | ITD method | Method in [30] | Relay 1 | Relay 2 | Relay 1 | Relay 2 |
| 12.5% | 0.01 | 0.001 | 0.151 | 0.001 | 0.380 | 50 | 0.003 | 0.158 | — | — | 100 | 0.006 | 0.143 | — | — |
| 20.0% | 0.01 | 0.009 | 0.066 | 0.001 | 0.380 | 50 | 0.006 | 0.082 | — | — | 100 | 0.009 | 0.066 | — | — |
| 50.0% | 0.01 | 0.028 | 0.028 | 0.001 | 0.380 | 50 | 0.032 | 0.024 | — | — | 100 | 0.038 | 0.020 | — | — |
| 80.0% | 0.01 | 0.104 | 0.004 | 0.380 | 0.001 | 50 | 0.110 | 0.003 | — | — | 100 | 0.116 | 0.003 | — | — |
| 87.5% | 0.01 | 0.151 | 0.001 | 0.380 | 0.001 | 50 | 0.152 | 0.001 | — | — | 100 | 0.157 | 0.001 | — | — |
|
|