Research Article
Parametric Evaluation of the Flow Boiling Heat Transfer Properties of R22 and R407c inside Horizontal Microfin Tube
Table 1
Properties of working refrigerants [
35,
36].
| Refrigerant | R22 | R407c | Composition | Pure | Blended (R32 (23%), R125 (25%), R134a (52%)) | ASHRAE safety guideline | A1 | A1 | ODP | 0.055 | 0 | GWP | 1810 | 1530 | (kg. Kmol-1) | 86.468 | 86.2 | (kPa) | 4977.37 | 4619.11 | (K) | 369.15 | 359.89 | Thermophysical properties of refrigerants | Property | R22 | R407c | (K) | 293.15 | 313.15 | 293.15 | 313.15 | (kg.m-3) | 1209.9 | 1128.5 | 1158.7 | 1067.8 | (kPa) | 910.02 | 1533.6 | 1037.6 | 1748.9 | (kJ.Kg-1) | 187.60 | 166.60 | 189.02 | 164.06 | (J.g-1 K-1) | 1.2356 | 1.3389 | 1.505 | 1.657 | (N.m-1) | 0.0088 | 0.006036 | 0.0077 | 0.0049 | (W.m-1 K-1) | 0.0857 | 0.0766 | 0.0885 | 0.0785 | (μPa.s) | 173.70 | 138.67 | 173.56 | 133.15 |
|
|