Islanding Event Detection in Grid-Connected Distributed Generation Systems Using Unscented Kalman Filter
Table 7
Comparison of the proposed method.
| Islanding detection method | Small/large power discrepancy during islanding accurately detected/total cases | Test-description balanced/unbalanced load joining during normal condition accurately detected/total cases | Balanced/unbalanced load separation during normal condition accurately detected/total cases | Speed (cycles) | Accuracy (%) | Computational burden |
| OVP/UVP | 16/20 | 16/20 | 16/20 | 5 to 6 | 81.6 | Low | Wavelet transform | 17/20 | 17/20 | 18/20 | 1 to 2 | 88.3 | High | Superimposed | 18/20 | 16/20 | 18/20 | 1 to 2 | 86.6 | Medium | Component | | | | | | | Proposed method | 19/20 | 18/20 | 18/20 | 1 to 2 | 91.6 | Low |
|
|