Research Article

Comparative Performance Study of Dissolved Gas Analysis (DGA) Methods for Identification of Faults in Power Transformer

Table 10

Identified fault in “T-11” based on the Doernenburg ratio method.

Gas ratioConcentration (ppm)

CH4/H2 ()1200/13000.9
C2H2/C2H4 ()200/3700.5
C2H2/CH4 ()200/12000.1
C2H6/C2H2 ()630/2003.1
Corona (low-intensity PD)