Research Article

Comparative Performance Study of Dissolved Gas Analysis (DGA) Methods for Identification of Faults in Power Transformer

Table 16

Performance accuracy comparison of each DGA method.

Total cases Roger’s ratio methodIEC ratio methodDoernenburg ratio methodDuval triangle methodThree-ratio methodRelative percentage of four gas methodsKey gas method

Number of total predictions 22222222222222
Total right predictions 15161118201719
Total wrong predictions 76114253
Total accuracy 68%72%50%81%90%77%86%