Research Article

Comparative Performance Study of Dissolved Gas Analysis (DGA) Methods for Identification of Faults in Power Transformer

Table 4

Overheating in conductor fault identified based on Roger’s ratio code.

Ratio codeGas ratioConcentration (ppm)Code

CH4/H2140/1520.90
C2H6/CH495/1400.60
C2H4/C2H6282/952.91
C2H2/C2H467/2820.20
Overheating in conductors