Research Article

Development and Application of a Fuzzy Control System for a Lead-Acid Battery Bank Connected to a DC Microgrid

Table 3

Response parameters of the DC bus voltage.

Controller typeSettling timeOvershootPeak timeError at steady state

PI8 seconds5.52%2.4 seconds1.31%
PD + I fuzzy4 seconds5.2%1.6 seconds0.65%