Line and load data for BATA feeder.

Sending node ()Receiving node ()Conductor typeLength (km)Resistance (Ω)Reactance (Ω)Receiving end load (kW)Receiving end load (kVAr)

12AAC951.860.573810.39934224.67612.408
23AAC950.2910.0897740.0624789.966.69
34AAC950.3810.1175390.08180169.3462.26
45AAC950.6790.2094720.14578125.7710.59
56AAC950.290.0894650.0622630.000.00
67AAC951.1060.3412010.23745825.975015.8430
78AAC950.5550.1712180.1191590.000.00
89AAC950.4740.1462290.10176848.0025.80
310AAC500.9030.5225660.39388981.7171.11
1011AAC500.2730.1579850.119083136.7463.84
612AAC250.4990.5893190.41641675.4554.22
1213AAC950.7110.2193440.1526520.000.00
1314AAC500.4570.2644660.19934363.9044.65
1315AAC501.2760.7384210.55659180.4052.80
1516AAC250.1030.1216430.08595441.9821.80
1617AAC250.7060.8337860.58915788.2866.93
1718AAC500.3470.2008090.1513615.083.06
819AAC500.2450.1417820.106869113.0046.82
1920AAC951.1230.3464460.24110885.0762.20
2021AAC250.5180.6117580.43227155.6038.99
2122AAC500.50.289350.21810.000.00
2223AAC500.4240.2453690.18494927.2212.02
2224AAC500.280.1620360.12213628.0412.59
2425AAC502.1211.2274230.92518155.8137.96
2526AAC250.1880.2220280.15688674.6055.23
2627AAC250.2750.3247750.22948846.5224.54
2228AAC250.630.7440300.52573548.4093.80
2829AAC500.3280.1898140.1430749.305.50
2930AAC500.3180.1840270.13871234.4517.37
3031AAC500.1970.1140040.08593125.7848.74
2932AAC500.2420.1400460.10556178.5047.80
3233AAC500.3790.2193280.16531998.0066.00
3334AAC950.0910.0280740.01953893.5086.00