Table 6

Voltage THD at each bus for different PV penetration levels.

Buses0%10%20%30%40%50%60%70%80%90%100%

10.760.770.780.790.800.820.830.850.860.870.90
20.770.780.800.810.941.221.271.361.531.701.87
30.770.790.810.831.001.251.281.481.681.862.05
40.770.780.790.881.081.431.451.651.862.072.28
50.760.800.840.981.231.641.671.942.202.452.70
60.760.760.861.021.301.731.772.072.342.612.88
70.760.780.971.211.572.092.192.562.903.233.56
80.760.801.021.311.702.272.412.803.183.553.91
90.760.801.021.311.702.272.412.803.183.553.91
100.770.730.760.831.001.311.281.481.671.862.05
110.770.730.760.831.001.311.281.481.671.862.05
120.760.760.861.021.301.731.772.072.342.612.88
130.760.760.861.021.301.731.772.072.342.612.88
140.760.760.861.031.301.731.772.072.342.612.88
150.760.760.861.021.301.731.772.072.342.612.87
160.760.760.861.021.301.731.772.072.342.612.87
170.760.760.861.021.301.731.772.072.342.612.87
180.760.760.861.021.301.731.772.072.342.612.87
190.760.821.081.401.832.432.603.033.433.834.22
200.760.861.201.602.112.793.033.534.004.464.92
210.760.941.441.982.633.463.814.435.035.606.17
220.760.991.572.182.893.794.214.895.546.186.81
230.760.991.572.182.893.794.214.895.546.186.81
240.760.991.572.182.893.794.214.895.546.186.81
250.760.991.572.182.893.794.214.895.546.176.80
260.760.991.572.182.893.794.214.895.546.176.80
270.760.991.572.182.893.794.214.895.546.176.80
280.761.111.882.663.534.605.175.996.797.568.33
290.761.151.972.793.714.825.436.297.137.948.74
300.761.151.972.793.714.825.436.297.137.948.74
310.761.151.972.793.714.825.436.297.137.948.74
320.761.172.042.893.844.995.626.527.388.229.05
330.761.222.143.054.045.245.926.867.778.659.53
340.751.222.153.074.075.275.966.907.828.709.58