Research Article
Power Quality and Performance Analysis of Grid-Connected Solar PV System Based on Recent Grid Integration Requirements
Table 7
THDi and TDDi at PCC for different PV penetration levels.
| Cases | THDi | (A) | (A) | (A) | | TDDi | Max. TDDi |
| Case 0 | 0.56 | 4.77 | 73.33 | 15970 | 217.78 | 0.04 | 15.0 | Case 1 | 43.81 | 4.90 | 73.33 | 16030 | 218.60 | 2.93 | 15.0 | Case 2 | 37.72 | 11.30 | 73.33 | 16090 | 219.42 | 5.81 | 15.0 | Case 3 | 34.84 | 18.18 | 73.33 | 16140 | 220.10 | 8.64 | 15.0 | Case 4 | 33.33 | 25.15 | 73.33 | 16200 | 220.92 | 11.43 | 15.0 | Case 5 | 32.37 | 32.10 | 73.33 | 16260 | 221.74 | 15.50 | 15.0 | Case 6 | 31.73 | 38.99 | 73.33 | 16320 | 222.56 | 15.57 | 15.0 | Case 7 | 31.26 | 45.88 | 73.33 | 16370 | 223.24 | 19.59 | 15.0 | Case 8 | 30.88 | 52.73 | 73.33 | 16430 | 224.06 | 22.21 | 15.0 | Case 9 | 30.56 | 59.49 | 73.33 | 16490 | 224.87 | 24.79 | 15.0 | Case 10 | 30.28 | 66.29 | 73.33 | 16540 | 225.56 | 27.37 | 15.0 |
|
|