Fuzzy-Based EV Charging Station and DVR-Fed Voltage Compensation for a DFIG-Fed Wind Energy System during Grid Faults
Table 9
DVR compensated voltage with PI and fuzzy control.
| DVR controller | Fault voltage in p.u. | Compensated voltage in p.u. | Phase A | Phase B | Phase C | Phase A | Phase B | Phase C |
| Three-phase fault | PI | 0.3602 | 0.3613 | 0.3504 | 0.9564 | 1.184 | 0.9793 | Fuzzy | 0.3601 | 0.3614 | 0.3505 | 1.055 | 1.015 | 1.021 |
| Two-phase fault | PI | 1.02 | 0.3862 | 0.3265 | 1.02 | 1.169 | 1.088 | Fuzzy | 1.02 | 0.3864 | 0.3266 | 1.02 | 1.028 | 1.023 |
| Single-phase fault | PI | 1.027 | 1.012 | 0.3105 | 1.029 | 1.012 | 0.8846 | Fuzzy | 1.027 | 1.012 | 0.3103 | 1.021 | 1.01 | 1.044 |
|
|