Fuzzy-Based EV Charging Station and DVR-Fed Voltage Compensation for a DFIG-Fed Wind Energy System during Grid Faults

Table 9

DVR compensated voltage with PI and fuzzy control.

DVR controllerFault voltage in p.u.Compensated voltage in p.u.
Phase APhase BPhase CPhase APhase BPhase C

Three-phase fault
PI0.36020.36130.35040.95641.1840.9793
Fuzzy0.36010.36140.35051.0551.0151.021

Two-phase fault
PI1.020.38620.32651.021.1691.088
Fuzzy1.020.38640.32661.021.0281.023

Single-phase fault
PI1.0271.0120.31051.0291.0120.8846
Fuzzy1.0271.0120.31031.0211.011.044