Research Article
Adaptive Parameter Estimation for Static Var Generators Based on Wind Speed Fluctuation of Wind Farms
Table 3
Traditional step-by-step identification results under a stable wind speed.
| | Estimated parameter | Real value | Observed quantity, P | Observed quantity, Q | | Estimated value | Error (%) | Estimated value | Error (%) |
| | Kdp | 0.1E − 3 | 9.71E − 5 | 2.900 | 9.82E − 5 | 1.800 | | Kdi | 0.02 | 0.0201 | 1.000 | 0.01998 | 0.200 | | Kqp | 5 | 5.0022 | 0.044 | 4.8682 | 2.600 | | Kqi | 1000 | 999.322 | 0.0687 | 989.231 | 1.076 | | KPI | 0.3 | 0.30081 | 0.270 | 0.2934 | 2.200 | | KII | 10 | 9.6501 | 3.499 | 10.028 | 0.280 | | L | 0.22 | 0.21889 | 0.505 | 0.2194 | 0.273 |
|
|