Research Article
Adaptive Parameter Estimation for Static Var Generators Based on Wind Speed Fluctuation of Wind Farms
Table 5
Parameter estimation results and errors using conventional and proposed hybrid estimation.
| | Estimated parameter | Real value | Multimode hybrid estimate | Error (%) | Conventional estimate | Error (%) |
| | Kdp | 0.1E − 3 | 9.76E − 5 | 3.100 | 1.071E − 4 | 6.300 | | Kdi | 0.02 | 0.0201 | 0.500 | 0.0210 | 5.000 | | Kqp | 5 | 4.9986 | 0.028 | 4.766 | 4.680 | | Kqi | 1000 | 998.80 | 0.120 | 978 | 2.200 | | KPI | 0.3 | 0.2986 | 0.470 | 0.2854 | 4.480 | | KII | 10 | 9.981 | 0.190 | 10.18 | 1.800 | | L | 0.22 | 0.217 | 1.300 | 0.2130 | 3.180 |
|
|