Optimal Load Distribution in DG Sources Using Model Predictive Control and the State Feedback Controller for Switching Control

Table 4

The numerical results for the islanding mode in the presence of the proposed DE-MPC controller.

Active powerInitial amount (MW)Intermediate amount (in the islanding mode) (MW)Final amount (MW)Recovery time (second) after reconnecting the grid (CB-1)

Figure 14PL10.70.680.70.02
PG10.63−0.120.630.02
P10.070.710.070.03
Voltage dropVoltage range, KV
(%) PPC1Initial amountIntermediate amount (in the islanding mode)
Proposed DE-MPC Figure 152.1%54.89
FS-MPC2.7%54.85
DSVM-MPC2.5%54.87
PL1 curveOV%Rise timeSettling time
PID3%0.08s0.25s
Proposed DE-MPC00.05s0.1 s