Research Article

An Investigation of the Electrical Properties of Pressboard Impregnated with Mineral Oil-Based Nanofluids at Different Concentrations of Fe3O4 Magnetic Nanoparticles

Table 5

Results of the AC breakdown strengths of the impregnated pressboard.

Impregnated Pressboard Samples withAC breakdown strengths (kV)SD
AveragekV/mm

Mineral Oil (MO)65.8441.150.36
MO + Fe3O4 (0.01%)69.1343.200.64
MO + Fe3O4 (0.03%)74.2946.430.45
MO + Fe3O4 (0.05%)71.7944.860.54

SD = Standard deviation of the data on AC tests.