A Novel Proposed Algorithm to Enhance the Overcurrent Relays’ Performance in Active Distribution Networks
Table 1
Three-phase fault current at near end and far end for each primary relay.
| Faulted section | Primary relay | Backup relay | Fault current | Near | Far |
| S1 | R1 | — | 1120 | 1100 | S2 | R2 | R1 | 1100 | 1058 | S3 | R3 | R2 | 1058 | 1021 | S4 | R4 | R3 | 1021 | 983 | S5 | R5 | R4 | 983 | 875 | S6 | R6 | R5 | 875 | 811 | S7 | R7 | R6 | 811 | 768 | S8 | R8 | R7 | 768 | 684 | S9 | R9 | R8 | 684 | 614 | S10 | R10 | R9 | 614 | 606 | S11 | R11 | R10 | 606 | 590 | S12 | R12 | R11 | 590 | 512 | S13 | R13 | R12 | 512 | 480 | S14 | R14 | R13 | 480 | 455 | S15 | R15 | R14 | 455 | 430 | S16 | R16 | R15 | 430 | 379 | S17 | R17 | R16 | 379 | 360 | S18 | R18 | R1 | 1100 | 1075 | S19 | R19 | R18 | 1075 | 858 | S20 | R20 | R19 | 858 | 801 | S21 | R21 | R20 | 801 | 710 | S22 | R22 | R2 | 1021 | 999 | S23 | R23 | R22 | 999 | 882 | S24 | R24 | R23 | 882 | 785 | S25 | R25 | R5 | 875 | 857 | S26 | R26 | R25 | 857 | 832 | S27 | R27 | R26 | 832 | 722 | S28 | R28 | R27 | 722 | 658 | S29 | R29 | R28 | 658 | 630 | S30 | R30 | R29 | 630 | 561 | S31 | R31 | R30 | 561 | 541 | S32 | R32 | R31 | 541 | 515 |
|
|