Techno-Economic Assessment of Voltage Sags Mitigation in Distribution System Connected to DGs

Table 6

Summary of simulation results of different values of DG and places when three-phase fault happens at each bus.

DG value MWFault at bus 1Fault at bus 2Fault at bus 3Fault at bus 4
Bus1 (PU)Bus2 (PU)Bus3 (PU)Bus4 (PU)Bus1 (PU)Bus2 (PU)Bus3 (PU)Bus4 (PU)Bus1 (PU)Bus2 (PU)Bus3 (PU)Bus4 (PU)Bus1 (PU)Bus2 (PU)Bus3 (PU)Bus4 (PU)

DG location00.5940.5880.5850.5750.5960.5910.580.5820.6350.590.5860.590.6270.60.590.588
DG at bus 420.6010.5930.5910.60.6020.5920.5930.60.6090.5920.5920.6050.6360.60.5920.598
40.5970.5910.5950.6040.5990.590.5930.6050.6110.5920.5940.6050.6370.5970.5930.6
5.50.5980.590.5950.6050.5970.5910.5950.6050.6110.5930.5950.6070.6440.6010.5920.603
70.6020.5950.60.6110.6020.5960.6010.6090.6120.5950.5960.6120.6450.6030.5940.606
DG at bus 320.6050.5950.5960.5930.6030.5950.5950.5930.6110.5950.5970.5930.6450.5970.5940.592
40.6040.5950.5970.5950.6030.5950.5990.5960.6130.5920.60.5970.6420.6010.5950.593
5.50.6030.5960.6010.5960.6020.5940.6010.5960.6130.5940.6010.5970.6430.6020.5960.593
70.6050.5970.6050.6040.6040.5950.6040.6020.6140.5960.6030.6010.6450.6040.5990.596
DG at bus 220.6070.60.5910.5870.6080.5950.590.5910.6190.6000.5910.5910.650.6080.5920.591
40.6080.60.5930.590.6060.5990.5910.5890.6200.6010.5920.5920.6510.6120.5930.592
5.50.6050.6030.5920.590.6080.5990.5930.590.6190.6010.5930.5920.6530.6150.5950.594
70.6080.6060.5950.5930.6090.6010.5960.5930.6210.6030.5940.5940.6560.6160.5950.595
DG at bus 120.6130.5950.5850.5830.6090.5940.5860.5840.6270.5980.5910.5910.6590.6090.5920.591
40.6140.5940.5870.5840.6110.5940.5850.5850.630.5990.5920.5930.660.6100.5930.592
5.50.6150.5940.5860.5850.6140.5950.5870.5830.6320.60.5920.5920.6620.6110.5950.593
70.6150.5960.5890.5860.6150.5960.5890.5910.6360.6010.5930.5930.6630.6120.5960.595