Low Computational Burden Adaptive Overcurrent Protection for Active Distribution Networks

Table 5

Operating time for the proposed adaptive and conventional protection approach for variation in DERs powers.

DER stateRelayConventionalProposed
123FPRBR

0.2510.25F1R3R10.4620.6590.1960.4620.6650.203
F2R5R30.0960.4880.3920.0960.4890.394
F3R6R30.2860.4880.2020.2860.4890.203
F4R8R60.0970.2980.2010.0970.2990.202

10.51F1R3R10.4590.6590.2000.4400.6630.203
F2R5R30.0970.4850.3880.0970.4890.392
F3R6R30.2900.4850.1950.2900.4900.200
F4R8R60.0980.3010.2030.0980.3030.205

0.20.50.75F1R3R10.4630.6590.1960.4630.6680.205
F2R5R30.0980.4880.3910.0980.4920.394
F3R6R30.2910.4880.1970.2910.4920.201
F4R8R60.0990.3030.2040.0990.3030.205

The times in column delta t for conventional and proposed approaches are bolded when relay misscoordination is presented for the conventional approach. In this situation, adequate relay coordination was obtained using the proposed approach.