Low Computational Burden Adaptive Overcurrent Protection for Active Distribution Networks

Table 6

Operating times for the islanded condition.

DER stateRelayConventionalProposed
123FPRBR

011F1R2R40.0920.2880.1950.0920.2950.202
F2R6R80.0990.3010.2020.0990.3010.202

010F1R2R40.0910.2860.1940.0910.2920.201
F2R8R60.1000.2980.1980.1000.3020.202

0.510.25F1R2R40.0900.2860.1960.0900.2910.201
F2R6R80.1000.2980.1980.1000.3000.201

The times in column delta t for conventional and proposed approaches are bolded when relay misscoordination is presented for the conventional approach. In this situation, adequate relay coordination was obtained using the proposed approach.