Conservation Voltage Reduction Strategy for Autonomous Microgrid with Improved Voltage-CurrentDroop-Based Inverter Control Framework

Table 2

Representation of power saving in 5 bus test system.

Conventional Q-V droop (V/Var) DG1: 1.7e − 3, DG2: 2e − 4, and DG3: 3e − 5Power saving (in %)
Conventional V-I droop (Ω) DG1: 0.231, DG2: 0.206, and DG3: 0.497
Modified V-I droop (Ω) DG1: 0.221, DG2: 0.216, and DG3: 0.464
Sl. noStep change in load (s)Voltage in case of Q-V droop (pu)Voltage in case of V–I droop (pu)Apparent power (Q-V droop)Apparent power (V-I droop)

1Base load1.00.99.228.14011.71
20.50.9890.92215.33013.20013.89
31.00.9800.93021.84018.45015.52
41.50.9730.94126.25024.8705.25