Research Article

Conservation Voltage Reduction Strategy for Autonomous Microgrid with Improved Voltage-CurrentDroop-Based Inverter Control Framework

Table 4

Representation of power saving in IEEE 9 bus test system.

Conventional Q-V droop (V/Var) DG1: 1.7e − 5, DG2: 2e − 4, DG3: 3e − 4, and DG4: 1e − 5Power saving (in %)
Conventional V-I droop (Ω) DG1: 0.401, DG2: 0.141, DG3: 0.092, and DG4: 0.098
Modified V-I droop (Ω) DG1: 0.421, DG2: 0.216, DG3: 0.164, and DG4: 0.155
Sl. noStep change in load (s)Voltage in case of Q-V droop (pu)Voltage in case of V-I droop (pu)Apparent power (Q-V droop)Apparent power (V-I droop)

1Base load1.00.918.5e316e313.5
20.50.9920.91723.8e321.2e310.9
31.00.9830.92631e327.8e310.3
41.50.9790.93137e335.5e34