Research Article
A Price-Based Load Flow Algorithm in Decentralized Distribution Markets
Table 1
The IEEE 33-bus distribution network data.
| Sending bus | Receiving bus | Feeder parameters | Receiving bus load | R (ohm) | X (ohm) | Pd (kW) | Qd (kVAr) |
| 1 | 2 | 0.0922 | 0.047 | 100 | 60 | 2 | 3 | 0.493 | 0.2511 | 90 | 40 | 3 | 4 | 0.366 | 0.1864 | 120 | 80 | 4 | 5 | 0.3811 | 0.1941 | 60 | 30 | 5 | 6 | 0.819 | 0.707 | 60 | 20 | 6 | 7 | 0.1872 | 0.6188 | 200 | 100 | 7 | 8 | 0.7114 | 0.2351 | 200 | 100 | 8 | 9 | 1.03 | 0.74 | 60 | 20 | 9 | 10 | 1.044 | 0.74 | 60 | 20 | 10 | 11 | 0.1966 | 0.065 | 45 | 30 | 11 | 12 | 0.3744 | 0.1238 | 60 | 35 | 12 | 13 | 1.468 | 1.155 | 60 | 35 | 13 | 14 | 0.5416 | 0.7129 | 120 | 80 | 14 | 15 | 0.591 | 0.526 | 60 | 10 | 15 | 16 | 0.7463 | 0.545 | 60 | 20 | 16 | 17 | 1.289 | 1.721 | 60 | 20 | 17 | 18 | 0.732 | 0.574 | 90 | 40 | 2 | 19 | 0.164 | 0.1565 | 90 | 40 | 19 | 20 | 1.5042 | 1.3554 | 90 | 40 | 20 | 21 | 0.4095 | 0.4784 | 90 | 40 | 21 | 22 | 0.7089 | 0.9373 | 90 | 40 | 3 | 23 | 0.4512 | 0.3083 | 90 | 50 | 23 | 24 | 0.898 | 0.7091 | 420 | 200 | 24 | 25 | 0.896 | 0.7011 | 420 | 200 | 6 | 26 | 0.203 | 0.1034 | 60 | 25 | 26 | 27 | 0.2842 | 0.1447 | 60 | 25 | 27 | 28 | 1.059 | 0.9337 | 60 | 20 | 28 | 29 | 0.8042 | 0.7006 | 120 | 70 | 29 | 30 | 0.5075 | 0.2585 | 200 | 600 | 30 | 31 | 0.9744 | 0.963 | 150 | 70 | 31 | 32 | 0.3105 | 0.3619 | 210 | 100 | 32 | 33 | 0.341 | 0.5302 | 60 | 40 |
|
|