Research Article

Optimal Sizing and Deployment of Renewable Energy Generators in Practical Transmission Network Using Grid-Oriented Multiobjective Harmony Search Algorithm for Loss Reduction and Voltage Profile Improvements

Table 10

Objective function values.

S. no.Objective functionsWithout REG unitsREG units with 2021 scenarioREG units with 2031 scenario
20212031One REGTwo REGThree REGOne REGTwo REGThree REG

1Total active power loss (MW)7.2713.943.091.170.826.914.493.95
2Total reactive power loss (MVAR)17.3133.187.352.791.9416.4410.689.41
3Total voltage deviation (p.u.)0.0550.0770.0440.0260.0170.0530.0370.036