Research Article

Optimal Sizing and Deployment of Renewable Energy Generators in Practical Transmission Network Using Grid-Oriented Multiobjective Harmony Search Algorithm for Loss Reduction and Voltage Profile Improvements

Table 6

Description of conductors of transmission lines.

S. no.Details of technical parametersNumerical magnitudes of technical parameter used for line conductors
Twin mooseACSR zebraACSR panther

1Positive sequence resistance (R1)0.0298 /km/circuit0.0749 /km/circuit0.1622 /km/circuit
2Positive sequence reactance (X1)0.332 /km/circuit0.3992 /km/circuit0.3861 /km/circuit
3Positive sequence susceptance (B/2)1.7344 × 10−6/km/circuit1.4670 × 10−6/km/circuit1.4635 × 10−6/km/circuit
4Zero sequence resistance (R0)0.1619 /km/circuit0.2200 /km/circuit0.4056 /km/circuit
5Zero sequence reactance (X0)1.24 /km/circuit1.3392 /km/circuit1.6222 /km/circuit
6Zero sequence susceptance1.12 × 10−6/km/circuit9.2004 × 10−7/km/circuit1.3171 × 10−7/km/circuit
7Line thermal rating515 MVA176 MVA71 MVA