International Transactions on Electrical Energy Systems / 2023 / Article / Tab 7 / Research Article
Optimal Sizing and Deployment of Renewable Energy Generators in Practical Transmission Network Using Grid-Oriented Multiobjective Harmony Search Algorithm for Loss Reduction and Voltage Profile Improvements Table 7 Description of transformers.
From node no. To node no. Transformer symbol Voltage ratio (kV) MVAR capacity (MVA) Values of transformer parameters 1 3 UT-1 400/220 3 × 315 Z 1 = 0.14 pu; (X1/R1) = 20; Z 0 = 0.14 pu; (X0/R0) = 202 4 UT-2 400/220 2 × 315 Z 1 = 0.14 pu; (X1/R1) = 20; Z 0 = 0.14 pu; (X0/R0) = 205 21 UT-3 220/132 3 × 100 Z 1 = 0.12 pu; (X1/R1) = 20; Z 0 = 0.12 pu; (X0/R0) = 208 20 UT-4 220/132 260 Z 1 = 0.12 pu; (X1/R1) = 20; Z 0 = 0.12 pu; (X0/R0) = 207 15 UT-5 220/132 570 Z 1 = 0.12 pu; (X1/R1) = 20; Z 0 = 0.12 pu; (X0/R0) = 206 14 UT-6 220/132 160 Z 1 = 0.12 pu; (X1/R1) = 20; Z 0 = 0.12 pu; (X0/R0) = 2010 37 UT-7 220/132 100 Z 1 = 0.12 pu; (X1/R1) = 20; Z 0 = 0.12 pu; (X0/R0) = 209 26 UT-8 220/132 kV 260 Z 1 = 0.12 pu; (X1/R1) = 20; Z 0 = 0.12 pu; (X0/R0) = 2011 44 UT-9 220/132 100 Z 1 = 0.12 pu; (X1/R1) = 20; Z 0 = 0.12 pu; (X0/R0) = 2012 46 UT-10 220/132 2 × 100 Z 1 = 0.12 pu; (X1/R1) = 20; Z 0 = 0.12 pu; (X0/R0) = 2013 62 UT-11 220/132 2 × 160 Z 1 = 0.12 pu; (X1/R1) = 20; Z 0 = 0.12 pu; (X0/R0) = 20