Research Article
Analysis of Pre- and during COVID-19 Mixed Load Models on Unbalanced Radial Distribution System Using a New Metaphor-Less Rao Optimization
Table 6
The phase wise result analysis for mixed LM during COVID-19 effect.
| Description | Phase A | Phase B | Phase C | APL (kW) | RPL (kVar) | MVV (p.u.) | VSI (p.u.) | APL (kW) | RPL (kVar) | MVV (p.u.) | VSI (p.u.) | APL (kW) | RPL (kVar) | MVV (p.u.) | VSI (p.u.) |
| Base case | 40.987 | 45.683 | 0.93850 | 0.77263 | 43.44 | 41.641 | 0.93798 | 0.77025 | 33.753 | 45.118 | 0.94461 | 0.79277 | Case 1 | 14.606 | 16.166 | 0.97059 | 0.88728 | 16.313 | 15.805 | 0.96906 | 0.87835 | 13.004 | 18.045 | 0.97043 | 0.88374 | Case 2 | 29.084 | 33.088 | 0.95784 | 0.8389 | 29.404 | 27.957 | 0.96085 | 0.84891 | 26.57 | 31.855 | 0.95697 | 0.83561 | Case 3 | 17.273 | 15.342 | 0.97944 | 0.92007 | 14.46 | 12.987 | 0.98045 | 0.92389 | 13.896 | 13.246 | 0.98161 | 0.92821 | Case 4 | 12.086 | 13.793 | 0.9707 | 0.88562 | 17.144 | 13.093 | 0.98065 | 0.92237 | 14.092 | 16.121 | 0.96692 | 0.87124 | Case 5 | 30.769 | 33.437 | 0.95381 | 0.82485 | 28.362 | 30.986 | 0.96819 | 0.87521 | 22.094 | 27.407 | 0.96904 | 0.87865 | Case 6 | 11.564 | 10.138 | 0.99282 | 0.96852 | 14.005 | 9.9302 | 0.99372 | 0.97126 | 16.507 | 14.36 | 0.97776 | 0.91065 | Case 7 | 13.802 | 14.459 | 0.97729 | 0.90932 | 12.613 | 12.392 | 0.96503 | 0.86389 | 9.7675 | 11.554 | 0.9717 | 0.88844 | Case 8 | 28.383 | 30.861 | 0.96285 | 0.8566 | 28.805 | 28.991 | 0.96555 | 0.86569 | 24.542 | 30.253 | 0.97357 | 0.89525 | Case 9 | 13.451 | 12.258 | 0.99566 | 0.98256 | 15.559 | 13.849 | 1 | 1 | 9.4786 | 11.708 | 0.9957 | 0.9796 |
|
|