Research Article
Wide-Area Damping Controller Design Based on the Frequency Domain Self-Excitation Method
Table 3
System indices for P=200MW.
| Alternative input signal | Residue index | geometric laterality index | frequency | Damping ratio | Compensation phase |
| the rotor speed difference of G1 and G3 | 0.3568 | 0.8951 | 0.6587 | 0.0473 | 97.2 |
| the active power of the AC line | 1.2302e-06i | 0.7501 | 0.6331 | 0.0035 | 115.5 |
| AC line current amplitude | 0.0117 | 0.7276 | 0.6245 | 0.0172 | 31.4 |
| difference of voltage phase between two sides of AC line | 1.4371e-08 | 0.7330 | 0.5891 | 0.0063 | 29.8 |
|
|