Research Article

An Improved Backward/Forward Sweep Power Flow Method Based on a New Network Information Organization for Radial Distribution Systems

Table 5

Results for IEEE 15-bus system.

NodeCIMPIDLFSMMProposed method

11111
20.971280.968850.970310.97017
30.956670.954270.955710.95657
40.95090.948520.949950.95078
50.949910.947540.948960.94977
60.958220.955830.957260.96267
70.954760.952370.95380.95974
80.956940.954550.955990.96115
90.967970.965550.9670.96020
100.966890.964480.965930.95936
110.949950.947570.9490.95202
120.945820.943460.944880.95006
130.944510.942150.943570.94842
140.94860.946230.947660.94926
150.948440.946060.947490.94775